Power factor and disadvantages of low pf

Short answer

Power factor is cos φ = P/S = kW/kVA. Low power factor causes higher line current for the same power, increased I²R losses, larger voltage drops, oversized and costlier equipment, reduced system capacity, and often penalty charges from utilities.

What is power factor in ac circuit? Disadvantages of low power factor.

Power factor is the cosine of the phase angle φ between the voltage and current in an AC circuit. It is also the ratio of active power to apparent power:

cos φ = P / S = R / Z = kW / kVA

It lies between 0 and 1, and is called lagging for inductive loads and leading for capacitive loads.

Disadvantages of low power factor

  • Large current for the same power. I = P/(V cos φ) for single phase, or P/(√3 V_L cos φ) for three phase. A low cos φ means a larger current.
  • Higher copper loss. Loss = I²R rises as 1/cos²φ in the cables, transformers and generator windings.
  • Poor voltage regulation. The large current causes a bigger voltage drop (IR and IX) in lines and transformers, so the load voltage falls.
  • Larger equipment size and cost. Generators, transformers, switchgear and cables must be rated in kVA, not kW, so they are bigger and costlier for the same useful power.
  • Reduced capacity. The same kVA rating delivers less kW (kW = kVA × cos φ), so a plant cannot supply as many loads.
  • Lower efficiency and heavier tariff. Utilities usually charge a penalty on low power factor (below about 0.8 to 0.9).