Effect of low power factor on equipment ratings

Short answer

Low power factor increases current for the same real power. Transformers need higher kVA rating and suffer poor voltage regulation. Generators must be derated. Cables require larger cross-section, leading to higher I²R losses and voltage drop.

How does the low power factor affect the rating of the transformers, generators and cables in distribution system of an industry?

At a given real power P and voltage V, current and kVA are inversely proportional to power factor:

I   = P / (√3 V cos φ)
kVA = kW / cos φ

So when pf falls, every component carrying this current must be larger, and losses rise.

1. Transformers

  • The rating of a transformer is in kVA, limited by winding current (heating) and core flux.
  • Lower pf → more kVA for the same kW, so a bigger transformer is needed.
  • Example: 800 kW load at pf 1.0 needs 800 kVA; at 0.8 it needs 1000 kVA; at 0.6 it needs 1333 kVA.
  • Copper loss ∝ I² ∝ 1/cos²φ – at pf 0.7 the copper loss is about 2 times that at unity pf.
  • Voltage regulation becomes poor with lagging pf (reactive voltage drop adds).

2. Generators (alternators, DG sets)

  • Rated in kVA at a stated pf (usually 0.8 lag). Below rated pf, the field current needed to hold voltage rises above design, so the alternator must be de-rated or a larger machine bought.
  • The prime mover is sized for kW; at low pf the prime mover is under-used while the alternator is at full current – poor utilisation.
  • Larger excitation system needed; poorer voltage regulation.

3. Cables and conductors

  • Cable size is chosen on current. Low pf increases current, so a larger cross-section is needed:
Cross-section ∝ I ∝ 1/cos φ
Copper volume (for same loss) ∝ 1/cos²φ
  • Higher I²R loss and voltage drop along the cable.

4. Switchgear and protective devices

  • Breakers, busbars, CTs and fuses must be rated for the higher current, adding to cost.

Summary table

EquipmentEffect of low pf
TransformerHigher kVA rating, higher Cu loss, poor regulation
GeneratorDe-rating, larger exciter, under-used prime mover
CableLarger size, more loss and voltage drop
SwitchgearHigher current rating
ConsumerHigher kVA demand charge / pf penalty

Numerical illustration: a 400 kW, 400 V load at 0.6 pf draws I = 400 000 / (√3 × 400 × 0.6) ≈ 962 A, but at 0.95 pf only ≈ 608 A. The transformer could be 421 kVA instead of 667 kVA.

Hence power factor correction with capacitors (target 0.95–0.98) is used to reduce equipment ratings, losses and kVA charges.

✓ Answer checked by Claude Opus 5.5 (high effort)