- 2068 Jestha (old course) · 8 marks
Effect of low power factor on equipment ratings
Short answer
Low power factor increases current for the same real power. Transformers need higher kVA rating and suffer poor voltage regulation. Generators must be derated. Cables require larger cross-section, leading to higher I²R losses and voltage drop.
How does the low power factor affect the rating of the transformers, generators and cables in distribution system of an industry?
At a given real power P and voltage V, current and kVA are inversely proportional to power factor:
I = P / (√3 V cos φ)
kVA = kW / cos φ
So when pf falls, every component carrying this current must be larger, and losses rise.
1. Transformers
- The rating of a transformer is in kVA, limited by winding current (heating) and core flux.
- Lower pf → more kVA for the same kW, so a bigger transformer is needed.
- Example: 800 kW load at pf 1.0 needs 800 kVA; at 0.8 it needs 1000 kVA; at 0.6 it needs 1333 kVA.
- Copper loss ∝ I² ∝ 1/cos²φ – at pf 0.7 the copper loss is about 2 times that at unity pf.
- Voltage regulation becomes poor with lagging pf (reactive voltage drop adds).
2. Generators (alternators, DG sets)
- Rated in kVA at a stated pf (usually 0.8 lag). Below rated pf, the field current needed to hold voltage rises above design, so the alternator must be de-rated or a larger machine bought.
- The prime mover is sized for kW; at low pf the prime mover is under-used while the alternator is at full current – poor utilisation.
- Larger excitation system needed; poorer voltage regulation.
3. Cables and conductors
- Cable size is chosen on current. Low pf increases current, so a larger cross-section is needed:
Cross-section ∝ I ∝ 1/cos φ
Copper volume (for same loss) ∝ 1/cos²φ
- Higher I²R loss and voltage drop along the cable.
4. Switchgear and protective devices
- Breakers, busbars, CTs and fuses must be rated for the higher current, adding to cost.
Summary table
| Equipment | Effect of low pf |
|---|---|
| Transformer | Higher kVA rating, higher Cu loss, poor regulation |
| Generator | De-rating, larger exciter, under-used prime mover |
| Cable | Larger size, more loss and voltage drop |
| Switchgear | Higher current rating |
| Consumer | Higher kVA demand charge / pf penalty |
Numerical illustration: a 400 kW, 400 V load at 0.6 pf draws I = 400 000 / (√3 × 400 × 0.6) ≈ 962 A, but at 0.95 pf only ≈ 608 A. The transformer could be 421 kVA instead of 667 kVA.
Hence power factor correction with capacitors (target 0.95–0.98) is used to reduce equipment ratings, losses and kVA charges.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Emergency power supply system for industry · Industrial Power Distribution and Illumination, chapter 9 · asked 2×
- Low earth resistance and equipment earthing methods · Industrial Power Distribution and Illumination, chapter 2
- Induction motor improving power factor · Industrial Power Distribution and Illumination, chapter 10
- Industry room 30 × 20 m LED lighting and DB · Industrial Power Distribution and Illumination, chapter 7 · asked 2×
- Causes of poor power factor and improvement · Industrial Power Distribution and Illumination, chapter 10
- Power vs lighting system and cable sizing factors · Industrial Power Distribution and Illumination, chapter 5
- Power factor and disadvantages of low pf · Basic Electrical Engineering, chapter 7 · asked 3×
- Low power factor causes, disadvantages · Basic Electrical Engineering, chapter 7
- Proximity effect in cables vs overhead lines · Power System Analysis I, chapter 4
- Weighted factor rating for choosing a site · Industrial Engineering and Management, chapter 2
All Industrial Power Distribution and Illumination chapter 10 questions →