- 2068 Bhadra (old course) · 8 marks
Causes of poor power factor and improvement
Short answer
Poor power factor is caused by induction motors, lightly loaded transformers, arc furnaces, discharge lamps; it raises current and losses. Improvement methods: static capacitors (most common), synchronous condensers, phase advancers, and over-excited synchronous motors to supply leading reactive power.
Write the causes of poor power factor in an electrical power system and discuss the method of improving it.
Power factor is the ratio of real power to apparent power, cos φ = kW/kVA. A pf well below 1 (lagging) is called poor; it means the load draws extra reactive current that does no useful work.
Causes of poor (lagging) power factor
- Induction motors – the main cause in industry. They need magnetising current; at full load pf is about 0.8–0.85, and at light load it falls to 0.2–0.3. Oversized or lightly loaded motors make it worse.
- Transformers – magnetising current, especially when lightly loaded or on no load (e.g. at night).
- Arc and induction furnaces, welding sets – operate at very low pf (about 0.3–0.6).
- Discharge lamps with magnetic ballasts – fluorescent, mercury and sodium lamps with choke have pf around 0.5.
- Higher supply voltage than rated increases magnetising current and lowers pf.
- Harmonics from rectifiers, drives and converters reduce the true (distortion) power factor.
- Reactors and chokes in the system.
Effects (why it must be improved)
Higher current for the same kW → larger kVA rating of generator, transformer and switchgear, larger cables, higher I²R losses, poorer voltage regulation, and penalty / higher kVA charges in the tariff.
Methods of improvement
Leading kVAR is supplied near the load to cancel lagging kVAR:
- Static capacitors – most common. Connected in star or delta across the supply, either fixed or automatically switched (APFC panel with relay). Low loss, little maintenance, no moving parts; but life is shortened by over-voltage and harmonics.
- Synchronous condenser – an over-excited synchronous motor on no load; gives smooth, stepless control of kVAR; used at large substations, costly and needs maintenance.
- Phase advancers – used with large induction motors; supply exciting ampere-turns to the rotor circuit at slip frequency so the motor runs at higher pf.
- Synchronous motors driving plant loads, run over-excited to supply leading kVAR.
Supply ──┬──── Motor load (lagging)
│
=== Capacitor bank (leading kVAR)
│
Placement of capacitors: individual (at motor terminals – best for loss reduction), group, or central (at main bus with automatic control).
Good practice: correct motor sizing, avoiding idle running of motors and transformers, and electronic ballasts also help keep pf high. Target pf is usually 0.95–0.99; going to unity is not economical.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Induction motor improving power factor · Industrial Power Distribution and Illumination, chapter 10
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
- Effect of low power factor on equipment ratings · Industrial Power Distribution and Illumination, chapter 10
- Types of power supply system for industrial plant · Industrial Power Distribution and Illumination, chapter 1 · asked 2×
- Emergency power supply system for industry · Industrial Power Distribution and Illumination, chapter 9 · asked 2×
- Power vs lighting system and cable sizing factors · Industrial Power Distribution and Illumination, chapter 5
- Low power factor causes, disadvantages · Basic Electrical Engineering, chapter 7
- Importance and improvement of power factor · Basic Electrical Engineering, chapter 7
- Causes, disadvantages and improvement of low pf · Utilization of Electrical Energy, chapter 6 · asked 2×
- Symmetrical angle control for power factor · Power Electronics, chapter 2
All Industrial Power Distribution and Illumination chapter 10 questions →