Line pf of 35 kW induction motor with capacitors

Short answer

The capacitor bank rating is fixed at 14.58 kVAR based on the half-load condition. With this capacitor, the line power factor becomes 0.994 lagging at full load and 0.271 leading at no load.

A 35 kW induction motor has pf 0.9 and efficiency 0.9 at full load, pf 0.6 and efficiency 0.7 at half load. At no load, the current is 25% of full load current and pf 0.1. Capacitors are supplied to make the line pf 0.8 at half load. With these capacitors in circuit, find the line pf at (i) full load (ii) no load.

The capacitor kVAR is fixed by the half-load condition and then stays connected at full load and at no load.

Input power and reactive power of the motor

Full load: output 35 kW, η=0.9\eta = 0.9, pf 0.9

PFL=350.9=38.89 kWQFL=PFLtan⁡ϕ=38.89×tan⁡(cos⁡−10.9)=38.89×0.4843=18.83 kVAR\begin{aligned} P_{FL} &= \frac{35}{0.9} = 38.89\ \text{kW} \\ Q_{FL} &= P_{FL}\tan\phi = 38.89 \times \tan(\cos^{-1}0.9) = 38.89 \times 0.4843 = 18.83\ \text{kVAR} \end{aligned}

Half load: output 17.5 kW, η=0.7\eta = 0.7, pf 0.6

PHL=17.50.7=25 kWQHL=25×tan⁡(cos⁡−10.6)=25×1.3333=33.33 kVAR\begin{aligned} P_{HL} &= \frac{17.5}{0.7} = 25\ \text{kW} \\ Q_{HL} &= 25 \times \tan(\cos^{-1}0.6) = 25 \times 1.3333 = 33.33\ \text{kVAR} \end{aligned}

No load: current is 25% of full-load current, pf 0.1

SFL=38.890.9=43.21 kVA,SNL=0.25×43.21=10.80 kVAPNL=10.80×0.1=1.080 kW,QNL=10.80×sin⁡(cos⁡−10.1)=10.75 kVAR\begin{aligned} S_{FL} &= \frac{38.89}{0.9} = 43.21\ \text{kVA}, \quad S_{NL} = 0.25 \times 43.21 = 10.80\ \text{kVA} \\ P_{NL} &= 10.80 \times 0.1 = 1.080\ \text{kW}, \quad Q_{NL} = 10.80 \times \sin(\cos^{-1}0.1) = 10.75\ \text{kVAR} \end{aligned}

Capacitor rating (line pf 0.8 at half load)

QC=PHL(tan⁡ϕ1−tan⁡ϕ2)=25(1.3333−0.75)=14.58 kVAR\begin{aligned} Q_C &= P_{HL}(\tan\phi_1 - \tan\phi_2) = 25(1.3333 - 0.75) = 14.58\ \text{kVAR} \end{aligned}

(i) Line pf at full load

Q′=18.83−14.58=4.25 kVAR (lagging)cos⁡ϕ=38.8938.892+4.252=0.994 lagging\begin{aligned} Q' &= 18.83 - 14.58 = 4.25\ \text{kVAR (lagging)} \\ \cos\phi &= \frac{38.89}{\sqrt{38.89^2 + 4.25^2}} = 0.994\ \text{lagging} \end{aligned}

(ii) Line pf at no load

Q′=10.75−14.58=−3.84 kVAR (leading)cos⁡ϕ=1.0801.0802+3.842=0.271 leading\begin{aligned} Q' &= 10.75 - 14.58 = -3.84\ \text{kVAR (leading)} \\ \cos\phi &= \frac{1.080}{\sqrt{1.080^2 + 3.84^2}} = 0.271\ \text{leading} \end{aligned}
LoadP (kW)Q motor (kVAR)Q net (kVAR)Line pf
Full38.8918.834.250.994 lag
Half25.0033.3318.750.800 lag
No load1.0810.75−3.840.271 lead

Answer: Capacitor =14.58= 14.58 kVAR; line pf (i) full load ≈0.994\approx 0.994 lagging, (ii) no load ≈0.271\approx 0.271 leading.