- 2072 Magh · 8 marks
Connected load, MD, demand, diversity, load factor
Short answer
Connected load = sum of nameplate ratings (e.g., 70 kW). Maximum demand = highest actual draw (e.g., 42 kW). Demand factor = MD/connected load (0.6). Diversity factor = sum of individual MDs / system MD (≥1, e.g., 1.25). Load factor = average load / MD (e.g., 0.5). High diversity factor reduces equipment size; high load factor lowers energy cost.
Explain with examples of following terminology: i) Connected load ii) Maximum demand iii) Demand factor iv) Diversity factor v) Load factor
These terms describe how much of the installed equipment is actually used and when. One example workshop is used for all of them.
Example workshop: 5 motors of 10 kW, lighting 5 kW and heaters 15 kW.
i) Connected load
The sum of the rated (nameplate) powers of all equipment connected to the supply.
Connected load = 5×10 + 5 + 15 = 70 kW
ii) Maximum demand
The greatest load drawn at any time in a period (usually the highest 15- or 30-minute average, read by an MD meter). Not all equipment runs at full load at once, so MD < connected load.
Recorded maximum demand = 42 kW
iii) Demand factor
The ratio of maximum demand to connected load (always ≤ 1).
Demand factor = MD / Connected load = 42/70 = 0.6
It is used to find the MD of a new installation from its connected load.
iv) Diversity factor
The ratio of the sum of individual maximum demands of parts of a system to the maximum demand of the whole system (always ≥ 1).
If the workshop and two other workshops have individual MDs of 42 kW, 30 kW and 28 kW, and the feeder's recorded MD is 80 kW:
Diversity factor = (42 + 30 + 28) / 80 = 100/80 = 1.25
A high diversity factor means smaller transformers and feeders can supply many loads that peak at different times.
v) Load factor
The ratio of average load to maximum demand over a period.
If the workshop uses 504 kWh in a day:
Average load = 504 / 24 = 21 kW
Load factor = 21 / 42 = 0.5
A high load factor means the plant capacity is used well and the cost per kWh is lower.
| Term | Formula | Range |
|---|---|---|
| Demand factor | MD / Connected load | ≤ 1 |
| Diversity factor | Σ individual MD / system MD | ≥ 1 |
| Load factor | Average load / MD | ≤ 1 |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Connected load, MD, demand factor, load factor · Industrial Power Distribution and Illumination, chapter 1
- Load centre, connected load, maximum demand · Industrial Power Distribution and Illumination, chapter 1
- Demand factor and diversity factor of substation · Industrial Power Distribution and Illumination, chapter 1
- Substation capacity and diversity factor from load pattern · Industrial Power Distribution and Illumination, chapter 1
- Load factor and demand factor numerical · Industrial Power Distribution and Illumination, chapter 1
- Need for diversity; maximum ratio combining · Wireless Communication, chapter 5
- Feedback vs maximum ratio combining diversity · Wireless Communication, chapter 5
All Industrial Power Distribution and Illumination chapter 1 questions →