- 2080 Chaitra · 4 marks
Transformer size for four blocks
Short answer
Max demand per block: 250×0.9=225, 200×0.8=160, 150×0.75=112.5, 400×0.85=340 kVA. Sum = 837.5 kVA. Plant max demand = 837.5/1.5 = 558.33 kVA. Next available size is 600 kVA. Select 600 kVA transformer.
There are four blocks in an industry having connected load of 250 kVA, 200 kVA, 150 kVA and 400 kVA and demand factor of 90%, 80%, 75% and 85% respectively. Use a diversity factor of 1.5. Calculate the size of transformer for the industry if transformer available in the market are 50kVA, 100kVA, 250kVA, 400kVA, 600kVA and 750kVA.
The transformer is sized on the maximum demand of the industry, found by applying demand factor to each block and then the diversity factor for the whole plant.
Step 1: maximum demand of each block
Max demand = connected load × demand factor
Block 1 = 250 × 0.90 = 225.0 kVA
Block 2 = 200 × 0.80 = 160.0 kVA
Block 3 = 150 × 0.75 = 112.5 kVA
Block 4 = 400 × 0.85 = 340.0 kVA
Sum of individual max demands = 837.5 kVA
Step 2: maximum demand of the industry
Diversity factor = sum of individual max demands
/ max demand of whole system
Max demand = 837.5 / 1.5 = 558.33 kVA
Step 3: select the transformer
Available sizes: 50, 100, 250, 400, 600, 750 kVA. The smallest size ≥ 558.33 kVA is 600 kVA.
Loading at peak = 558.33 / 600 = 93 %, which is acceptable.
Answer: maximum demand = 558.33 kVA; select one 600 kVA transformer. (If a future expansion margin of 20 % were added, 670 kVA would be needed and the 750 kVA unit would be chosen.)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Connected load, MD, demand, diversity, load factor · Industrial Power Distribution and Illumination, chapter 1
- Demand factor and diversity factor of substation · Industrial Power Distribution and Illumination, chapter 1
- Connected load, MD, demand factor, load factor · Industrial Power Distribution and Illumination, chapter 1
- Transformer size for given industry (figure) · Industrial Power Distribution and Illumination, chapter 4 · asked 2×
- Substation capacity and diversity factor from load pattern · Industrial Power Distribution and Illumination, chapter 1
- Connected load in an industry · Industrial Power Distribution and Illumination, chapter 1
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Equivalent circuit of 5 kVA 200/400 V transformer · Electrical Machines I, chapter 2 · asked 2×
- All-day efficiency of 150 kVA transformer · Electrical Machines I, chapter 2
- Half-load efficiency of 200 kVA transformer · Electrical Machines I, chapter 2
All Industrial Power Distribution and Illumination chapter 4 questions →