- 2080 Chaitra · 4 marks
Half-load efficiency of 200 kVA transformer
Short answer
Using full-load efficiency, total losses are 3.2653 kW; maximum efficiency at 3/4 load gives copper loss 2.0898 kW and iron loss 1.1755 kW. At half load copper loss is 0.5224 kW and efficiency = 80/(80 + 1.1755 + 0.5224) = 97.92%.
A 200 kVA transformer has an efficiency of 98 % at full load if the maximum efficiency occurs at three quarters of full load, calculate efficiency at half load. Assume negligible magnetizing current and 0.8 pf at all loads.
Maximum efficiency occurs when copper loss equals iron loss. Use this with the full-load efficiency to find both losses.
Losses at full load
Condition for maximum efficiency at 3/4 load
Efficiency at half load
Answer: efficiency at half load ≈ 97.92%.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Full-load and half-load efficiency of 100 kVA transformer · Electrical Machines I, chapter 2
- Full-load efficiency of 500 kVA transformer · Electrical Machines I, chapter 2
- Equivalent circuit and half-load efficiency of 50 kVA transformer · Electrical Machines I, chapter 2
- Efficiency of 25 kVA transformer at half load and overload · Electrical Machines I, chapter 2
- Iron loss and maximum efficiency of 20 kVA 220/2200 V transformer · Electrical Machines I, chapter 2 · asked 2×
- Iron loss and maximum efficiency of 20 kVA 250/2500 V transformer · Electrical Machines I, chapter 2 · asked 2×
- 500 kVA transformer efficiency, full and half load · Electrical Machines, chapter 2
- 500 kVA transformer efficiency full/half load · Electrical Machine, chapter 2
- 100 kVA transformer efficiency at full and half load · Electrical Machines, chapter 2
- 150 kVA transformer: max efficiency load · Electrical Machines, chapter 2