Transformer selection for apartment, residence, industry
Short answer
Apartment: total demand = Σ(flat loads × simultaneity factor) + common services, margin, round up. Residential house/colony: after-diversity demand per house × number of houses + street lighting, standard pole-mounted rating. Industry: kVA = kW/(η·pf), apply utillization and diversity, check largest motor voltage dip and harmonics, add expansion margin, select standard rating at 60-80% loading.
Discuss the methodology of selection of transformer for apartment building, residential building and industry.
The transformer for any building is chosen on its maximum demand, found from connected load reduced by utilization/demand factors and diversity (simultaneity) factors, plus a margin for growth, then rounded up to a standard rating.
Apartment building
- Find the load per flat (lights, sockets, kitchen, water heater, AC) e.g. 6–10 kVA.
- Apply a simultaneity factor that falls with the number of flats (e.g. 1.0 for 2–4 flats, about 0.78 for 5–9, 0.53 for 15–19, 0.4 for 50 or more flats).
- Add common services: lifts, water pumps, corridor lighting, fire pumps (with their own Ku and Ks).
- Add 20–25 % margin; usually one transformer (or two for reliability) with standby generator for lifts and pumps.
Residential building (individual house / colony)
- Small loads, high diversity; demand per house ≈ 2–5 kVA after diversity.
- Colony transformer = number of houses × after-diversity demand + street lighting; usually pole-mounted 50–250 kVA.
Industry
- Mostly motor loads: kVA = kW/(η·pf), Ku ≈ 0.75, plus lighting and heating (Ku = 1).
- Apply Ks per SDB and MDB depending on number of circuits and shift pattern.
- Check starting of the largest motor (voltage dip) and harmonics from drives.
- Consider separate or duplicate transformers for critical processes, and future expansion.
- Choose next standard rating (e.g. 250, 315, 400, 500, 630 kVA) so normal loading is about 60–80 %.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Transformer size for given industry (figure) · Industrial Power Distribution and Illumination, chapter 4 · asked 2×
- Transformer size for four blocks · Industrial Power Distribution and Illumination, chapter 4
- Transformer sizing and 11 kV feeder SLD · Industrial Power Distribution and Illumination, chapter 4
- Layout of indoor substation with single transformer · Industrial Power Distribution and Illumination, chapter 4
- kVAr and techno-economic analysis for 1000 kVA transformer · Industrial Power Distribution and Illumination, chapter 10
- Total cost of apartment building · Estimating and Costing, chapter 3
- Expansion joint in a residential building · Building Technology, chapter 10
- Quantity sheet and abstract for residential building · Estimating and Costing, chapter 2
- Fuse selection for 250 kVA transformer · Switchgear and Protection, chapter 3
All Industrial Power Distribution and Illumination chapter 4 questions →