Leading kVAR supplied by synchronous motor
Short answer
Factory: 240 kW at 0.8 lag => 180 kVAR lag. Combined 300 kW at 0.9 lag => 145.3 kVAR lag. Motor supplies 34.7 kVAR leading. Motor kVA = √(60²+34.7²)=69.31 kVA, pf = 0.866 leading.
A synchronous motor absorbing 60 kW is connected in parallel with a factory load of 240 kW having a lagging p.f. of 0.8. If the connected combined load has a p.f. of 0.9, what is the value of the leading kVAR supplied by the motor and at what p.f. is it working?
The synchronous motor is over-excited so it supplies leading kVAR, which cancels part of the lagging kVAR of the factory load.
Factory load
Combined load
kVAR from the motor
kVAR (lag +)
|
180 + factory load
|
145.3 + combined (pf 0.9)
| motor gives -34.7 kVAR
+--------------------------- kW
60 240 300
Answer: The motor supplies 34.70 kVAR leading and works at a power factor of 0.866 leading (input 69.31 kVA).
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Synchronous motor drawing lagging and leading current · Electric Machines II, chapter 2 · asked 4×
- Synchronous motor features and lagging/leading operation · Electric Machines II, chapter 2
- Synchronous motor adjusting to increasing load · Electric Machines II, chapter 2
- Internal emf and load angle of salient pole motor · Electric Machines II, chapter 2
- Open circuit emf and mechanical power of 75 kW motor · Electric Machines II, chapter 2
- Regulation of delta connected 1600 kVA alternator · Electric Machines II, chapter 1
- kW, kVA, kVAR in parallel impedances · Basic Electrical Engineering, chapter 7 · asked 2×
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
- Synchronous motor: pf when input rises to 1500 kW · Electrical Machines, chapter 6
- Annual saving by capacitors for 200 kW factory · Utilization of Electrical Energy, chapter 6