Annual saving by capacitors for 200 kW factory
Short answer
With 200 kW load, demand charge saving from improving pf 0.85 to 0.9 is Rs 1,960.80. Capacitors of 27.08 kVAR cost Rs 11,375; their loss costs Rs 338.60 and interest/depreciation Rs 1,137.50. Net annual saving is about Rs 485.
A factory takes a load of 200kW at 0.85 pf lagging for 2500 hrs per annum. The tariff is Rs. 150 per KVA plus 5 paisa per KWH consumed. If the pf is improved to 0.9 lagging by means of capacitors costing Rs 420 per KVAR and having a power loss of 100W per KVA, Calculate the annual saving effected by their use. Allow 10% per annum for interest and depreciation.
Saving comes from the reduced kVA demand charge; against it are the capacitor loss (extra kWh) and the interest and depreciation on capacitors. The capacitor kVAR is found from the 200 kW load, and the loss of 100 W per kVA of capacitor rating is taken as 0.1 kW per kVAR.
kVA demand before and after
Capacitor rating and its costs
Net annual saving
Answer: Annual saving ≈ Rs 485 (with 27.08 kVAR of capacitors).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Annual saving by pf improvement for 800 kW load · Utilization of Electrical Energy, chapter 6
- Annual charge and pf improvement (Rs 1300/kVA tariff) · Utilization of Electrical Energy, chapter 6 · asked 3×
- Annual charge and pf improvement (Rs 65/kVA tariff) · Utilization of Electrical Energy, chapter 6 · asked 3×
- Annual charge and pf improvement for 1200 kVA load · Utilization of Electrical Energy, chapter 6 · asked 3×
- Annual cost and saving with pf correction (400 kVA) · Utilization of Electrical Energy, chapter 6
- HV vs LV supply tariff for a factory · Utilization of Electrical Energy, chapter 6 · asked 2×
- Optimum pf under two-part tariff (200 kW) · Industrial Power Distribution and Illumination, chapter 10
- PF improvement of 1020 kVA factory load · Industrial Power Distribution and Illumination, chapter 10 · asked 2×
- Most economical power factor for 50 kW factory · Industrial Power Distribution and Illumination, chapter 10
- PF correction for 1250 kVA generator (+150 kW) · Industrial Power Distribution and Illumination, chapter 10