Temperature rise and tubes for 500 kVA transformer
Short answer
Plain tank rise 79.7 °C. Required tube area 9.698 m². With 50 mm diameter, 1.5 m long tubes, 42 needed. Arrangement: 14 tubes on each long side, 7 on each short side in a single row.
For a 500 kVA, 50 Hz, 6600/400, single phase core type, oil immersed, natural cooled power transformer, the design parameters are: Constant for output voltage per turn (K) = 0.8; Resistivity of copper = 0.021 Ω-mm²/m; Maximum flux density in core (Bm) = 1.5 Wb/m²; Current density = 2.75 A/mm²; Core type = Cruciform; Window space factor (Kw) = 0.27; Stacking factor (Ki) = 0.9; Ratio of height to width of windows (Hw/Ww) = 2.5; Ratio of yoke height to width (Hy/Dy) = 1; Axial depth of LV winding = 402 mm; Axial depth of HV winding = 377.5 mm; Inside diameter of LV winding = 310 mm; Outside diameter of LV winding = 348 mm; Inside diameter of HV winding = 360 mm; Outside diameter of HV winding = 418 mm; Taking iron loss = 1460 W, Copper loss = 3865 W at full load, Height of tank = 1.6 m, Length of tank = 1.05 m, Width of tank = 0.62 m, find the temperature rise. If the mean rise of oil is not to rise 35°C, find the necessary number of tubes and show its arrangement.
Only the losses and tank size are needed for this part; the core and winding data are used in the full design of the same transformer.
Basis
- A plain tank wall loses heat by radiation (≈ 6 W/m²°C) and natural convection (≈ 6.5 W/m²°C): total 12.5 W/m²°C.
- Tubes screen each other, so they add almost nothing by radiation, but they improve convection by about 35%: W/m²°C.
- Top and bottom of the tank are neglected.
Temperature rise with a plain tank
Total loss W.
This is far above the permitted mean oil rise of 35 °C, so cooling tubes are needed.
Number of tubes
Let the total tube area be :
Assume tubes of 50 mm diameter and 1.5 m mean length (tank height 1.6 m):
Check: W ≥ 5325 W.
Arrangement of tubes: with 50 mm tubes at 75 mm centre-to-centre spacing, one row round the tank can hold about tubes on each long side and on each short side. So 42 tubes are placed in a single row: 14 on each long side and 7 on each short side ().
o o o o o o o o o o o o o o (14)
+-------------------------------+
o | | o
o | | o
o | TANK (top view) | o
(7)o | 1.05 m x 0.62 m | o (7)
o | | o
o | | o
o | | o
+-------------------------------+
o o o o o o o o o o o o o o (14)
o = cooling tube, 50 mm dia, 75 mm pitch
Answer: temperature rise with plain tank ≈ 79.7 °C; 42 tubes of 50 mm diameter, 1.5 m long, keep the mean oil rise within 35 °C.
✓ Answer checked by Claude Sonnet 5.5
Related questions
- Design: 500 kVA single phase transformer with tubes · Electric Machine Design, chapter 3 · asked 2×
- Design: 150 kVA 6600/400 V distribution transformer · Electric Machine Design, chapter 3 · asked 5×
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 150 kVA 11000/440 V transformer with tubes · Electric Machine Design, chapter 3
- Design: 100 kVA 2200/480 V single phase transformer · Electric Machine Design, chapter 3 · asked 3×
- Design: 25 kVA transformer frame, regulation, tubes · Electric Machine Design, chapter 3 · asked 2×
- 3-phase 500 kVA transformer primary current · Electrical Machines, chapter 2
- 500 kVA 3-phase transformer efficiency · Electrical Machines, chapter 2