Capacitor size for maximum loss reduction (variant)

Short answer

The optimum capacitor size at node C is the resistance-weighted average of reactive flows: (146.34+86.34+60)/3 = 97.56 kVAR. Use 97.6 kVAR (≈100 kVAR standard).

For the 11 kV primary distribution network shown below, determine the size (kVAR) of the capacitor to be placed at the location shown in diagram to achieve the maximum loss reduction. For simplifying the analysis assume voltage at each node is 1 p.u. All impedances are in p.u. at 1000 kVA.

[Figure: radial feeder from a 1000 kVA, 33/11 kV source substation S to node A through impedance 1+j1, A to node B through 1+j1, B to node C through 1+j2. Loads through distribution transformers: 100 kVA at 0.8 p.f. lag at A, 50 kVA at 0.85 p.f. lag at B, 100 kVA at 0.8 p.f. lag at C. The capacitor is placed at node C.]

Method (optimum single capacitor)

With all node voltages taken as 1 p.u., the reactive current in a section equals its reactive power flow QiQ_i (p.u.). A shunt capacitor QcQ_c at the end node reduces the reactive flow in every section between the source and that node from QiQ_i to (Qi−Qc)(Q_i - Q_c). The loss reduction is

ΔPL=∑iRi[Qi2−(Qi−Qc)2]=∑iRi(2QiQc−Qc2)\begin{aligned} \Delta P_L &= \sum_i R_i\left[Q_i^2-(Q_i-Q_c)^2\right] = \sum_i R_i\left(2Q_iQ_c-Q_c^2\right) \end{aligned}

For maximum loss reduction, d(ΔPL)dQc=∑iRi(2Qi−2Qc)=0\dfrac{d(\Delta P_L)}{dQ_c} = \sum_i R_i(2Q_i-2Q_c)=0, so

Qc,opt=∑iRiQi∑iRiQ_{c,opt} = \frac{\sum_i R_iQ_i}{\sum_i R_i}

i.e. the optimum capacitor equals the resistance-weighted average of the reactive flows in the sections it relieves. The ratio does not depend on whether RR is in ohms or p.u., so kVAR can be used directly.

 S --(1+j1)-- A --(1+j1)-- B --(1+j2)-- C
              |            |            |
          100 kVA       50 kVA      100 kVA
          0.8 lag      0.85 lag     0.8 lag   [Qc]

Reactive load at each node

NodeS (kVA)p.f.sin⁡ϕ\sin\phiQ (kVAR)
A1000.80.660.00
B500.850.526826.34
C1000.80.660.00

Reactive flow in each section

SectionR (p.u.)Q flow (kVAR)R × Q
S–A160 + 26.34 + 60 = 146.34146.34
A–B126.34 + 60 = 86.3486.34
B–C160.0060.00
Total3292.68

Optimum capacitor

Qc=146.34+86.34+601+1+1=292.683=97.56 kVARQ_c = \frac{146.34+86.34+60}{1+1+1} = \frac{292.68}{3} = 97.56\ \text{kVAR}

In p.u. on 1000 kVA: Qc=0.0976Q_c = 0.0976 p.u.

Check of the loss reduction (p.u. on 1000 kVA):

ΔPL=∑Ri(2QiQc−Qc2)=2(0.09756)(0.29268)−3(0.09756)2=0.02855 p.u.≈28.6 kW\begin{aligned} \Delta P_L &= \sum R_i(2Q_iQ_c - Q_c^2)\\ &= 2(0.09756)(0.29268) - 3(0.09756)^2 = 0.02855\ \text{p.u.} \approx 28.6\ \text{kW} \end{aligned}

The capacitor is larger than the 60 kVAR load at C because it also relieves the heavier flows in S–A and A–B. In practice the nearest standard bank (about 100 kVAR) would be used.

Answer: Optimum capacitor at node C ≈ 97.6 kVAR (≈ 100 kVAR standard).