- Asked 5/20
- 2075 Bhadra · 6 marks
Capacitor size for maximum loss reduction (variant)
Short answer
The optimum capacitor size at node C is the resistance-weighted average of reactive flows: (146.34+86.34+60)/3 = 97.56 kVAR. Use 97.6 kVAR (≈100 kVAR standard).
For the 11 kV primary distribution network shown below, determine the size (kVAR) of the capacitor to be placed at the location shown in diagram to achieve the maximum loss reduction. For simplifying the analysis assume voltage at each node is 1 p.u. All impedances are in p.u. at 1000 kVA.
[Figure: radial feeder from a 1000 kVA, 33/11 kV source substation S to node A through impedance 1+j1, A to node B through 1+j1, B to node C through 1+j2. Loads through distribution transformers: 100 kVA at 0.8 p.f. lag at A, 50 kVA at 0.85 p.f. lag at B, 100 kVA at 0.8 p.f. lag at C. The capacitor is placed at node C.]
Method (optimum single capacitor)
With all node voltages taken as 1 p.u., the reactive current in a section equals its reactive power flow (p.u.). A shunt capacitor at the end node reduces the reactive flow in every section between the source and that node from to . The loss reduction is
For maximum loss reduction, , so
i.e. the optimum capacitor equals the resistance-weighted average of the reactive flows in the sections it relieves. The ratio does not depend on whether is in ohms or p.u., so kVAR can be used directly.
S --(1+j1)-- A --(1+j1)-- B --(1+j2)-- C
| | |
100 kVA 50 kVA 100 kVA
0.8 lag 0.85 lag 0.8 lag [Qc]
Reactive load at each node
| Node | S (kVA) | p.f. | Q (kVAR) | |
|---|---|---|---|---|
| A | 100 | 0.8 | 0.6 | 60.00 |
| B | 50 | 0.85 | 0.5268 | 26.34 |
| C | 100 | 0.8 | 0.6 | 60.00 |
Reactive flow in each section
| Section | R (p.u.) | Q flow (kVAR) | R × Q |
|---|---|---|---|
| S–A | 1 | 60 + 26.34 + 60 = 146.34 | 146.34 |
| A–B | 1 | 26.34 + 60 = 86.34 | 86.34 |
| B–C | 1 | 60.00 | 60.00 |
| Total | 3 | 292.68 |
Optimum capacitor
In p.u. on 1000 kVA: p.u.
Check of the loss reduction (p.u. on 1000 kVA):
The capacitor is larger than the 60 kVAR load at C because it also relieves the heavier flows in S–A and A–B. In practice the nearest standard bank (about 100 kVAR) would be used.
Answer: Optimum capacitor at node C ≈ 97.6 kVAR (≈ 100 kVAR standard).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Capacitor size, four-node 11 kV feeder · Transmission and Distribution System Design, chapter 7 · asked 5×
- Capacitor size for maximum loss reduction · Transmission and Distribution System Design, chapter 7 · asked 5×
- Capacitor size, feeder with 500 kVA end load · Transmission and Distribution System Design, chapter 7 · asked 5×
- Capacitor size, feeder with three equal loads · Transmission and Distribution System Design, chapter 7
All Transmission and Distribution System Design chapter 7 questions →