- Practice · 8 marks
Supply air quantity for a conditioned room
Short answer
Room sensible heat factor is 0.80. Using sensible load and 11 K temperature difference, mass flow is 1.60 kg/s. From latent load, supply specific humidity is 0.00876 kg/kg (≈88% RH). Volume flow is about 1.32 m³/s (79 m³/min).
A room is to be maintained at 25 °C and 50% RH. The room sensible heat gain is 18 kW and the latent heat gain is 4.5 kW. Air is supplied at 14 °C. Determine (a) the room sensible heat factor, (b) the mass flow rate of supply air, (c) the specific humidity and relative humidity of the supply air, and (d) the volume flow rate of supply air. Take kPa, kJ/kg, kJ/kg K and kJ/kg K. The saturation pressure at 25 °C is 3.169 kPa.
Room state
(a) Room sensible heat factor
(b) Supply air mass flow (from the sensible load)
( is found in step (c), and the two steps are iterated; the values converge after two or three trials.)
(c) Supply air humidity (from the latent load)
Relative humidity at 14 °C: the vapour pressure of the supply air is kPa, and the saturation pressure at 14 °C is about 1.598 kPa, so
The supply enthalpy is kJ/kg.
(d) Volume flow of supply air
Answer: (a) RSHF = 0.80; (b) 1.60 kg/s; (c) = 0.00876 kg/kg, RH about 88 %; (d) about 1.32 m³/s (79 m³/min).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sensible heating of air numerical · Applied Thermodynamics, chapter 4
- Cooling and dehumidifying coil load · Applied Thermodynamics, chapter 4
- Adiabatic mixing of two air streams · Applied Thermodynamics, chapter 4
- Properties of moist air numerical · Applied Thermodynamics, chapter 4
- Gain factor K1 raising overshoot from 25% to 50% · Control Systems, chapter 3 · asked 4×
- Adiabatic air turbine: mass flow and areas · Fundamental of Thermodynamics & Heat Transfer, chapter 4 · asked 2×
- Coolant heat rejection and radiator air flow · Automotive Technology, chapter 4
- Air compressor: heat transfer rate · Fundamental of Thermodynamics & Heat Transfer, chapter 4