Short answer

Room sensible heat factor is 0.80. Using sensible load and 11 K temperature difference, mass flow is 1.60 kg/s. From latent load, supply specific humidity is 0.00876 kg/kg (≈88% RH). Volume flow is about 1.32 m³/s (79 m³/min).

A room is to be maintained at 25 °C and 50% RH. The room sensible heat gain is 18 kW and the latent heat gain is 4.5 kW. Air is supplied at 14 °C. Determine (a) the room sensible heat factor, (b) the mass flow rate of supply air, (c) the specific humidity and relative humidity of the supply air, and (d) the volume flow rate of supply air. Take p=101.325p = 101.325 kPa, hfg=2501h_{fg} = 2501 kJ/kg, cpa=1.005c_{pa} = 1.005 kJ/kg K and cpv=1.88c_{pv} = 1.88 kJ/kg K. The saturation pressure at 25 °C is 3.169 kPa.

Room state

pv=0.5×3.169=1.585 kPa,ωr=0.622×1.585101.325−1.585=0.00988 kg/kgp_v = 0.5 \times 3.169 = 1.585\ \text{kPa},\qquad \omega_r = 0.622 \times \frac{1.585}{101.325 - 1.585} = 0.00988\ \text{kg/kg} hr=1.005×25+0.00988(2501+47)=50.3 kJ/kgh_r = 1.005 \times 25 + 0.00988(2501 + 47) = 50.3\ \text{kJ/kg}

(a) Room sensible heat factor

RSHF=QsQs+Ql=1818+4.5=0.80\text{RSHF} = \frac{Q_s}{Q_s + Q_l} = \frac{18}{18 + 4.5} = 0.80

(b) Supply air mass flow (from the sensible load)

Qs=m˙a cpm(tr−ts),cpm=1.005+1.88 ωs≈1.0215Q_s = \dot m_a\,c_{pm}(t_r - t_s),\qquad c_{pm} = 1.005 + 1.88\,\omega_s \approx 1.0215 m˙a=181.0215×(25−14)=1.602 kg/s=5767 kg/h\dot m_a = \frac{18}{1.0215 \times (25 - 14)} = 1.602\ \text{kg/s} = 5767\ \text{kg/h}

(ωs\omega_s is found in step (c), and the two steps are iterated; the values converge after two or three trials.)

(c) Supply air humidity (from the latent load)

Ql=m˙a(ωr−ωs) hfgQ_l = \dot m_a(\omega_r - \omega_s)\,h_{fg} ωr−ωs=4.51.602×2501=1.123×10−3\omega_r - \omega_s = \frac{4.5}{1.602 \times 2501} = 1.123 \times 10^{-3} ωs=0.00988−0.00112=0.00876 kg/kg\omega_s = 0.00988 - 0.00112 = 0.00876\ \text{kg/kg}

Relative humidity at 14 °C: the vapour pressure of the supply air is pv=ωsp/(0.622+ωs)=1.407p_v = \omega_s p/(0.622 + \omega_s) = 1.407 kPa, and the saturation pressure at 14 °C is about 1.598 kPa, so

ϕs=pvps=1.4071.598=0.88  (≈88 %)\phi_s = \frac{p_v}{p_s} = \frac{1.407}{1.598} = 0.88\ \ (\approx 88\ \%)

The supply enthalpy is hs=36.2h_s = 36.2 kJ/kg.

(d) Volume flow of supply air

vs=0.287×287.15 (1+1.608×0.00876)101.325=0.8248 m3/kgv_s = \frac{0.287 \times 287.15\,(1 + 1.608 \times 0.00876)}{101.325} = 0.8248\ \text{m}^3/\text{kg} V˙s=1.602×0.8248=1.321 m3/s (≈79.3 m3/min)\dot V_s = 1.602 \times 0.8248 = 1.321\ \text{m}^3/\text{s}\ (\approx 79.3\ \text{m}^3/\text{min})

Answer: (a) RSHF = 0.80; (b) 1.60 kg/s; (c) ωs\omega_s = 0.00876 kg/kg, RH about 88 %; (d) about 1.32 m³/s (79 m³/min).

✓ Answer checked by Claude Opus 5.5 (high effort)

All Applied Thermodynamics chapter 4 questions →