Sensible heating of air numerical
Short answer
With constant ω = 0.00742 kg/kg, v₁ = 0.8259 m³/kg gives ṁ_a = 200/0.8259 = 242 kg/min. Enthalpies: h₁ = 33.84 kJ/kg, h₂ = 49.13 kJ/kg. Heat transfer Q = (242/60)×(49.13−33.84) = 61.7 kW. Leaving RH = p_v/p_s,₃₀ = 1.194/4.247 = 0.281 (28%).
Air at 15 °C and 70% relative humidity flows at 200 m³/min into a heating coil and leaves at 30 °C. Find (a) the mass flow rate of dry air, (b) the heat transfer rate in the coil, and (c) the relative humidity of the air leaving the coil. Take kPa; saturation pressure at 15 °C is 1.706 kPa and at 30 °C is 4.247 kPa.
Sensible heating means is constant.
Inlet state
Enthalpies, :
(a) Mass flow of dry air
(b) Heat transfer
(c) Final relative humidity
Answer: (a) 242 kg/min dry air; (b) about 61.7 kW; (c) 28 %.