Short answer
Set K=10 for Ka=10. Uncompensated PM is –30.4°. Two identical lead stages with α=0.1716 are needed. Gc(s)=((1+0.397s)/(1+0.0681s))^2 gives Ka=10 s⁻² and PM=39.4° (≥35°).
The open loop transfer function of a unity feedback system is given by G(s) = K/[s²(0.2s+1)]. Design a lead compensator to meet the following specifications: Acceleration error constant = 10, Phase margin = 35°.
A type-2 plant has phase at low frequency, so the plant pole makes it unstable for any . A phase-lead network is designed on the Bode plot: , (unity DC gain, so is set by ).
Step 1: Gain for
Step 2: Uncompensated phase margin
Step 3: Phase lead required
This is more than about , which a single lead network cannot give with a sensible . Use two identical lead stages in cascade. Also, the plant magnitude falls at to dB/decade, so the crossover moves a lot and its phase falls quickly; a first trial with gives only . So take :
Step 4: New gain crossover
The two stages together add dB at . So is where ( dB):
Step 5: Corner frequencies
Step 6: Compensator and check
At : plant phase , compensator phase , so .
| Quantity | Uncompensated | Compensated |
|---|---|---|
| Gain crossover | 2.94 rad/s | 6.08 rad/s |
| Phase margin | ||
| Gain margin | negative (unstable) | 11.5 dB at 14.5 rad/s |
| 10 s | 10 s |
Answer: two cascaded lead stages, , give and .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Lead compensator for k/[s²(1+0.25s)], Ka = 10, PM 35° · Control Systems, chapter 7 · asked 5×
- Lead compensator for K/[s(1+0.2s)], Kv=10, PM=50° · Control Systems, chapter 7 · asked 2×
- Lead compensator for k/[s²(s+5)], Ka = 5, PM 30° · Control Systems, chapter 7
- Lead compensator for K/[s(1+0.2s)], Kv≥20, PM≥44° · Control Systems, chapter 7 · asked 2×
- Lead compensator for 2/[s(1+0.5s)], Kv > 20, PM 50° · Control Systems, chapter 7
- Lead compensator for 5/[(s+2)(s+20)], Kv ≥ 20 · Control Systems, chapter 7
- Lead compensator for K/[s(s+10)(s+2)], Kv ≥ 800 · Control Systems, chapter 7
- Bode design: PM 55°, GM 10 dB, Kv = 5 · Digital Control System, chapter 4