Short answer

PI controller Gc(s)=Kp+Ki/s adds a pole at the origin and a zero, raising system type by one to eliminate steady-state error. Example: DC motor G(s)=10/(s+2) with PI 4+8/s yields type-1, zero offset, and fast first-order response time constant 0.025 s.

Discuss the application of a PI controller with suitable example.

A PI controller produces a control signal proportional to both the error and the integral of the error:

u(t)=Kpe(t)+Ki∫0te(t) dt,Gc(s)=Kp+Kis=Kp(s+Ki/Kp)su(t) = K_p e(t) + K_i \int_0^t e(t)\,dt, \qquad G_c(s) = K_p + \frac{K_i}{s} = \frac{K_p\left(s + K_i/K_p\right)}{s}

It adds a pole at the origin and a zero at s=−Ki/Kps = -K_i/K_p.

Why it is applied

  • The pole at the origin raises the system type by one. A type-0 plant gets zero steady-state error to a step; a type-1 plant gets zero error to a ramp.
  • It removes the steady-state offset that a pure P controller always leaves.
  • The zero, placed close to the origin, limits the extra phase lag, so stability is not badly affected.
  • It acts like a lag compensator (low-pass), so it also filters high-frequency noise.
  • Drawbacks: slightly slower response, possibly more overshoot, and integral wind-up when the actuator saturates.

Example: speed control of a DC motor

Let the motor (speed output) be G(s)=10s+2G(s) = \dfrac{10}{s+2} with unity feedback (type 0).

  • With P control Kp=4K_p = 4: KP=lim⁡s→040s+2=20K_P = \lim_{s\to0} \dfrac{40}{s+2} = 20, so the step error ess=11+20=0.048e_{ss} = \dfrac{1}{1+20} = 0.048, i.e. a 4.8% speed offset that grows when load torque is applied.
  • With PI control Gc=4+8sG_c = 4 + \dfrac{8}{s}:
GcG=4(s+2)s⋅10s+2=40sG_c G = \frac{4(s+2)}{s}\cdot\frac{10}{s+2} = \frac{40}{s}

The system becomes type 1, KP=∞K_P = \infty and ess=0e_{ss} = 0. The closed loop is 40s+40\dfrac{40}{s+40}, a fast first-order response with time constant 0.025 s and no offset, even under constant load disturbances.

Other common uses: liquid-level and flow control, temperature control of furnaces, pressure control in process plants and voltage regulators, wherever zero steady-state offset is essential.