Speed control methods of DC shunt motor
Describe different methods of controlling the speed of shunt DC motor (armature control and field control methods).
The speed of a DC motor is N = (V − I_aR_a) / (KΦ), i.e. N ∝ E_b / Φ. So the speed can be changed by changing the flux Φ, the resistance in the armature circuit, or the applied voltage V.
1. Field control (flux control)
A rheostat R_f is connected in series with the shunt field.
(+) o----+------------------+
| |
[Rf] rheostat (M) armature, Ra
| |
[Shunt field] |
| |
(-) o----+------------------+
- Increasing the field resistance decreases I_f and Φ, so the speed rises above the base speed.
- Advantages: simple, cheap, small power loss (the field current is small), and smooth control.
- Limits: only speeds above normal; the range is about 3:1; commutation gets worse and the motor may become unstable at a very weak field.
2. Armature control
(a) Armature resistance control: a variable resistance R_e is inserted in series with the armature.
- Speed falls as R_e increases, because E_b = V − I_a(R_a + R_e) decreases while the flux stays at full value.
- Gives speeds below normal at constant torque.
- Drawbacks: a large I_a²R_e loss, poor efficiency, speed that depends on the load, and a resistance that must carry the full armature current. Used for short-duration duty or small motors.
(b) Armature voltage control (Ward-Leonard system)
AC motor -> DC generator (variable field) -> DC motor (field const.)
- The motor armature is fed from a separate generator whose output is varied smoothly from zero to maximum by its field rheostat.
- Speed varies smoothly in both directions, even through zero. Combined with field control, it gives a wide range (up to about 30:1).
- Disadvantages: high initial cost (three machines), lower efficiency and large floor space. Modern drives use thyristor or chopper control instead.
| Method | Speed range | Torque | Remarks |
|---|---|---|---|
| Field control | above base | constant power | cheap, efficient |
| Armature resistance | below base | constant torque | wasteful |
| Ward-Leonard | both sides | constant torque and power | costly, smooth |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Speed control methods of shunt DC motor · Electrical Machines, chapter 4 · asked 2×
- Shunt motor speed with 1 Ω armature resistance added · Electrical Machines I, chapter 4 · asked 5×
- Shunt motor speed with 1.2 Ω armature resistance added · Electrical Machines I, chapter 4 · asked 5×
- Shunt motor speed with 0.1 Ω armature resistance added · Electrical Machines I, chapter 4 · asked 4×
- Shunt motor speed with 0.1 Ω armature resistance, less load · Electrical Machines I, chapter 4 · asked 3×
- Shunt motor speed with 0.05 Ω armature resistance added · Electrical Machines I, chapter 4 · asked 3×
- DC shunt motor armature torque · Basic Electrical and Electronics Engineering, chapter 2
- Shunt motor speed with 50 Ω field resistance (1200 rpm) · Electrical Machines I, chapter 4 · asked 5×
- Shunt motor speed with field resistance added (250 V, 1400 rpm) · Electrical Machines I, chapter 4 · asked 5×
- Shunt motor speed with 50 Ω field resistance and lower torque · Electrical Machines I, chapter 4 · asked 4×