Induction motor current with load; stator connection
Short answer
As load increases, rotor slows, slip rises, boosting rotor current and torque; stator current automatically rises to balance rotor MMF and maintain flux. Stator winding connection: star reduces phase voltage to VL/√3, limiting starting current and torque to one-third of delta, used for star-delta starting.
How does an induction motor adjust its current with the changes in shaft load? Explain the effect of type of connection of stator winding of slip ring induction motor.
How the motor adjusts its current with load
An induction motor behaves like a transformer with a rotating secondary.
- At no load, the rotor runs near and the slip is tiny, so the rotor emf and the rotor current are very small. The stator takes only the no-load current (mostly magnetising, power factor 0.1 to 0.2).
- When the shaft load increases, the load torque exceeds the electromagnetic torque and the rotor slows down.
- The slip increases, so the relative speed between the field and the rotor increases. The rotor emf and its frequency increase, so the rotor current increases. The rotor power factor also improves.
- The torque therefore rises until it matches the load, and the motor settles at a new speed with slightly higher slip.
- The rotor mmf opposes the stator flux (Lenz's law) and tends to reduce it. To keep the flux constant (), the stator draws an extra current :
So the stator current rises automatically with load, and the input power factor improves with load.
Effect of stator connection (slip-ring motor)
The stator can be connected in star or delta (the rotor is normally star). For the same line voltage :
| Quantity | Star | Delta |
|---|---|---|
| Phase voltage | ||
| Phase current (relative) | 1/√3 of delta | 1 |
| Line current | 1/3 of delta | 1 |
| Torque () | 1/3 of delta | 1 |
- A delta-connected winding is used for normal running; it takes more current but delivers full torque.
- Star connection at starting reduces the starting current to one third and also gives one third of the torque (star-delta starter for delta-rated motors).
- The rotor connection does not change the stator current directly. With a star-connected rotor, the phase emf is , where is the emf between slip rings; this sets the rotor current and the values of the external resistance.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Starting, no-load and full-load current of slip ring motor · Electrical Machines I, chapter 5
- Slip ring motor: starting, no-load, full-load currents · Electrical Machines, chapter 5
- Slip ring motor: rotor current at 4% slip · Electrical Machines, chapter 5
- Slip ring motor max-torque slip and full-load output · Electrical Machines I, chapter 5 · asked 4×
- Slip for maximum torque and full-load output of slip ring motor · Electrical Machines I, chapter 5 · asked 2×
- Effect of five-times rotor resistance on 40 kW slip ring motor · Electrical Machines I, chapter 5
- 6-pole slip-ring IM no-load current · Electrical Machine, chapter 5
- IM and sync motor current adjust with load · Electrical Machine, chapter 5
- Slip power recovery for slip ring induction motor · Utilization of Electrical Energy, chapter 3 · asked 2×
- Slip-ring IM starting and running current · Electrical Machine, chapter 5