- 2076 Baisakh · 6 marks
Interconnected system SLD and functions of each part
Short answer
Generation converts primary energy to electricity at11 kV. Transmission carries bulk power at132–400 kV from plants to load centers and interconnects grids. Distribution steps down voltage to11 kV and400/230 V and supplies consumers through primary and secondary networks.
Draw a single line diagram of an interconnected power system showing generation, transmission and distribution systems and describe the function of each system.
Single line diagram
[G] 11 kV Step-up Transmission
|---->[11/220 kV]====== 220/400 kV ======+
|
[G] 11 kV [220/132 kV]
|---->[11/132 kV]====== 132 kV ====== Grid S/S
|
Sub-transmission 66/33 kV
|
[33/11 kV] S/S
|
Primary distribution 11 kV
|
[11/0.4 kV] DT
|
Secondary 400/230 V consumers
Function of each system
1. Generation system
- Converts primary energy (water, fuel, sun) into electrical energy in power stations at 6.6–11 kV.
- Includes turbines, alternators, exciters, governors and step-up transformers.
- Controls frequency (through governors) and voltage (through AVR).
2. Transmission system
- Carries bulk power from generating stations to major load centres at extra-high voltage (400, 220, 132 kV in Nepal).
- Interconnects power stations and neighbouring grids, allowing power exchange, sharing of reserve and economic dispatch.
- Includes towers, conductors, insulators, grid substations and protection.
- High voltage reduces current, losses and conductor cost.
Sub-transmission (66/33 kV) links grid substations to distribution substations in cities and districts.
3. Distribution system
- Delivers power from distribution substations (33/11 kV) to individual consumers.
- Primary distribution at 11 kV feeds distribution transformers and bulk consumers.
- Secondary distribution at 400 V (3-phase) / 230 V (1-phase) supplies houses, shops and small industries.
- Includes feeders, distributors, service mains, distribution transformers and meters.
| System | Voltage | Main function |
|---|---|---|
| Generation | 11 kV | Produce power |
| Transmission | 132–400 kV | Bulk transfer, interconnection |
| Sub-transmission | 33–66 kV | Feed local substations |
| Distribution | 11 kV, 400/230 V | Supply consumers |
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Interconnected system SLD with bus voltages · Power System Analysis I, chapter 1
- Interconnected system SLD, isolated vs interconnected, advantages · Power System Analysis I, chapter 1
- SLD of interconnected system vs isolated system · Power System Analysis I, chapter 1
- SLD with voltage levels and why three-phase · Power System Analysis I, chapter 1
- Single line diagram and its significance · Power System Analysis I, chapter 3
- Interconnected power system and advantages · Power System Analysis I, chapter 1
- Distribution substation with single line diagram · Industrial Power Distribution and Illumination, chapter 4
- Interconnected system and transmission planning · Transmission and Distribution System Design, chapter 1
- Advantages of interconnected power system · Power System Analysis II, chapter 1 · asked 3×
- Real power/frequency control in interconnected system · Power System Analysis II, chapter 1