String of 5 insulators on 100 kV, ratio 0.1

Short answer

With m = 0.1 and phase voltage 100/√3 = 57.735 kV, disc voltages (tower toline) are 8.00 kV, 8.80 kV, 10.48 kV, 13.21 kV, 17.25 kV. String efficiency = 57.735/(5×17.254) = 66.92%.

A string of 5 insulators is connected across a 100 kV line. If the ratio of shunt to self-capacitance is 0.1, determine the voltage distribution along the string and string efficiency.

Assumption: 100 kV is the line voltage of a three-phase line, so the voltage across each string is the phase voltage.

Data

  • Phase voltage V=100/3=57.735V = 100/\sqrt3 = 57.735 kV
  • Ratio of shunt to self-capacitance m=0.1m = 0.1
  • Discs numbered 1 (tower end) to 5 (line end)

Voltage distribution

Using Vk+1=Vk+m(V1+⋯+Vk)V_{k+1} = V_k + m(V_1+\dots+V_k):

V2=1.1V1V3=1.1V1+0.1(2.1V1)=1.31V1V4=1.31V1+0.1(3.41V1)=1.651V1V5=1.651V1+0.1(5.061V1)=2.1571V1\begin{aligned} V_2 &= 1.1V_1\\ V_3 &= 1.1V_1 + 0.1(2.1V_1) = 1.31V_1\\ V_4 &= 1.31V_1 + 0.1(3.41V_1) = 1.651V_1\\ V_5 &= 1.651V_1 + 0.1(5.061V_1) = 2.1571V_1 \end{aligned} V=7.2181V1  ⇒  V1=57.7357.2181=7.999 kVV = 7.2181V_1 \;\Rightarrow\; V_1 = \frac{57.735}{7.2181} = 7.999\ \text{kV}
DiscVoltage (kV)% of VV
1 (tower end)7.99913.85 %
28.79915.24 %
310.47818.15 %
413.20622.87 %
5 (line end)17.25429.88 %

String efficiency

η=V5V5=57.7355×17.254=66.92 %\eta = \frac{V}{5V_5} = \frac{57.735}{5\times 17.254} = 66.92\ \%

Answer: The disc voltages are 8.00, 8.80, 10.48, 13.21 and 17.25 kV, and the string efficiency is 66.92 %. If 100 kV is instead taken as the voltage across the string, every disc voltage scales by 3\sqrt3 (to 13.85, 15.24, 18.15, 22.87 and 29.88 kV), and the efficiency stays at 66.92 %.