Water tower foundation on weak stratum

Short answer

Using Boussinesq’s equation for a circular area: with q=Q/(πR²)=229.2 kN/m², R/z=5/3, stress Δσz = q[1 − 1/(1+(R/z)²)^(3/2)] = 198 kN/m². This exceeds the weak stratum’s bearing capacity of 100 kN/m², so the tower is unsafe.

A water tower has a circular foundation of diameter 10 m. The total weight of the tower including the foundation is 1800 tonnes (18000 kN). A very weak stratum having a bearing capacity of 10 t/m² (100 kN/m²) lies 3 m below the foundation level. Calculate the stress due to the foundation load at the top of the weak stratum and ascertain whether it will be safe to construct the water tower at that place with the given foundation size. (The 2076 paper does not print the depth of the weak stratum.)

Given

Circular foundation D=10D = 10 m (R=5R = 5 m). Load Q=18000Q = 18000 kN. Weak stratum at z=3z = 3 m below the foundation level (assumed, as the depth is not printed), bearing capacity qa=100q_a = 100 kN/m².

Contact pressure:

q=QπR2=18000π×52=229.2 kN/m2q = \frac{Q}{\pi R^2} = \frac{18000}{\pi \times 5^2} = 229.2\ \text{kN/m}^2

Stress at the top of the weak stratum (below the centre)

Boussinesq's equation for a uniformly loaded circular area:

Δσz=q[1−1(1+(R/z)2)3/2]\Delta\sigma_z = q\left[1 - \frac{1}{\left(1 + (R/z)^2\right)^{3/2}}\right] Rz=53=1.667,1+(R/z)2=3.778,(3.778)3/2=7.343\frac{R}{z} = \frac{5}{3} = 1.667, \qquad 1 + (R/z)^2 = 3.778, \qquad (3.778)^{3/2} = 7.343 Δσz=229.2[1−17.343]=229.2×0.8638=198.0 kN/m2\Delta\sigma_z = 229.2\left[1 - \frac{1}{7.343}\right] = 229.2 \times 0.8638 = 198.0\ \text{kN/m}^2

(A quick check by the 2:1 method: Q/[π4(10+3)2]=135.6Q/[\frac{\pi}{4}(10+3)^2] = 135.6 kN/m², also above 100.)

Check

Δσz=198 kN/m2≈19.8 t/m2>100 kN/m2 (10 t/m2)\Delta\sigma_z = 198\ \text{kN/m}^2 \approx 19.8\ \text{t/m}^2 > 100\ \text{kN/m}^2\ (10\ \text{t/m}^2)

Answer: The stress at the top of the weak stratum is about 198 kN/m², which exceeds the bearing capacity of the stratum (100 kN/m²). It is not safe to construct the water tower with this foundation size.

The foundation must be enlarged (a diameter of about 15 m gives about 97 kN/m²) or the load shifted to a deeper stratum (piles).