Non-destructive testing methods for concrete

Short answer

Key NDT methods: rebound hammer (surface hardness, IS 13311-2), ultrasonic pulse velocity (uniformity, cracks, IS 13311-1), combined SONREB, penetration resistance, pull-out, cover meter, half-cell potential, radiography, and impact echo. They provide indirect strength estimates and locate internal flaws.

Explain the methods (techniques) of non-destructive testing of concrete.

NDT methods give indirect estimates of strength, quality and condition without damaging the structure.

MethodWhat it measuresStandard / note
Rebound hammerSurface hardness, related to strengthIS 13311 Part 2
Ultrasonic pulse velocityPulse velocity, uniformity, voids, cracksIS 13311 Part 1
Combined (SONREB)Rebound number plus UPV for better strength estimate
Penetration resistance (Windsor probe)Depth of a probe fired into the surfaceSurface strength
Pull-out / pull-off testForce to pull out an embedded insertLocal strength
Cover meter / ferroscanCover and bar position by magnetic fieldCover check
Half-cell potentialProbability of rebar corrosionASTM C876
Radiography, gamma rayInternal voids and barsSpecial safety needs
Infrared thermography, impact echo, GPRDelamination, voidsSpecial tools
Carbonation depth (phenolphthalein)Depth of carbonated layerSemi-destructive

Rebound hammer (Schmidt hammer) test (IS 13311 Part 2)

Principle: a spring-loaded mass strikes the concrete surface through a plunger. The rebound of the mass, read as the rebound number RR on a scale of 10 to 100, depends on the surface hardness, which is related to strength.

Procedure

  1. Select a smooth, clean, dry surface of a structural member at least 100 mm thick; grind off plaster, loose scale and rough texture.
  2. Hold the hammer at right angles to the surface (a horizontal shot is the reference; shots vertically up or down need an orientation correction), push the plunger until the mass is released, and read the rebound number.
  3. Take about 9 to 12 readings at spots 20 to 50 mm apart; reject readings that differ from the mean by more than 6 units, and average the rest.
  4. Read the compressive strength from the manufacturer's calibration curve (for the position of the hammer), which should preferably be made from cubes of the same concrete.

Precautions: avoid edges, honeycombed and wet surfaces, and spots over reinforcement; the instrument should be checked on the test anvil.

Limits: it tests only the surface (about 30 mm), so it is affected by carbonation, moisture, surface finish, type of aggregate and cement, and age. Accuracy of strength is about ±15 to 25%. It is useful for comparing uniformity and for choosing places for coring or UPV.

Ultrasonic pulse velocity (UPV) test (IS 13311 Part 1)

Principle: the velocity of an ultrasonic pulse through concrete depends on its density and elastic properties. Sound, dense concrete transmits the pulse faster than porous or cracked concrete.

Apparatus: pulse generator and receiver with two transducers (usually 54 kHz), a timer reading to 0.1 microsecond, a coupling gel, and a reference calibration bar.

Procedure

  1. Calibrate the instrument on the reference bar.
  2. Clean the surface and apply grease or gel to ensure good acoustic contact.
  3. Put the transducers on the concrete, either directly (opposite faces, most reliable), semi-directly (adjacent faces) or indirectly (same face, least reliable).
  4. Measure the path length LL and the transit time TT.
  5. Calculate the velocity:
V=LTV = \frac{L}{T}

Take several readings and average them. Avoid paths parallel to reinforcement, as steel carries the pulse faster.

Quality of concrete (IS 13311 Part 1)

Pulse velocity (km/s)Quality
Above 4.5Excellent
3.5 to 4.5Good
3.0 to 3.5Medium
Below 3.0Doubtful (poor)

A combination of two or more methods gives a better estimate, and the results are best correlated with some cores.