Non-destructive tests on insulators

Short answer

Non-destructive tests include insulation resistance and polarization index (megger), dielectric loss factor tan δ by Schering bridge, partial discharge measurement for voids, and dissolved gas analysis for oil-filled equipment. They detect moisture, contamination, and ageing without damaging the insulation.

Explain different non-destructive tests that are carried out for different types of insulators.

Non-destructive tests check the quality and condition of insulation at voltages near or below the working voltage, without damaging it. They find moisture, contamination, voids and ageing early, so faults can be corrected before a destructive failure. The main tests are measurement of resistance, dielectric constant and loss (tan⁡δ\tan\delta), and partial discharges.

1. Measurement of insulation (DC) resistance and resistivity

  • A DC voltage (500 V – 10 kV, from a megger or DC source) is applied and the leakage current is measured with a sensitive galvanometer or electrometer.
  • A three-terminal (guard ring) electrode system separates volume current from surface leakage, giving volume resistivity ρv\rho_v and surface resistivity ρs\rho_s.
  • Polarization index PI=R10 min/R1 minPI = R_{10\,min}/R_{1\,min} shows moisture and dirt: PI>2PI > 2 is good, PI<1PI < 1 is dangerous.
  • Used on transformers, machines, cables and insulator units.

2. Measurement of dielectric constant and loss factor (tan⁡δ\tan\delta)

            HV
          /    \
     Cx,Rx      Cs (standard)
        |        |
        A--[D]---B
        |        |
       R3     R4 || C4
          \    /
          earth
  • The high-voltage Schering bridge is balanced; then
Cx=CsR4R3,tan⁡δ=ωC4R4C_x = C_s\frac{R_4}{R_3}, \qquad \tan\delta = \omega C_4 R_4
  • εr=Cx/C0\varepsilon_r = C_x/C_0 (C0C_0 = capacitance with vacuum/air). A rise in tan⁡δ\tan\delta with voltage ("tip-up") or with time indicates moisture, voids and ageing.
  • The transformer ratio-arm bridge is used for higher accuracy and for earthed specimens.
  • Used on bushings, cables, CTs, capacitors and machine windings.

3. Partial discharge (PD) measurement

  • Partial discharges in voids, cracks or at sharp edges produce small current pulses. They are detected with a coupling capacitor and a detection impedance in parallel with the test object (straight detection or balanced bridge circuit), and displayed on a PD detector/oscilloscope.
  • The result is the apparent charge in picocoulombs (pC), the inception and extinction voltages, and the pulse pattern (phase-resolved).
  • Calibrated by injecting a known charge q=V0C0q = V_0 C_0.
  • Acoustic (ultrasonic) and UHF sensors locate PD in transformers and GIS.

4. Other non-destructive tests

  • DC leakage current / step voltage test on cables and machines.
  • Dissolved gas analysis and oil BDV tests for oil-filled equipment.
  • Visual, ultrasonic and infrared (thermography) inspection for cracks and hot spots in insulators.
  • Leakage current monitoring of surge arresters (third-harmonic resistive current).

Tests by type of insulation

Insulation / equipmentMain non-destructive tests
Porcelain/glass/polymer line insulatorsIR (megger), visual, IR thermography, PD/corona
Bushings, CTs, capacitorsCapacitance and tan⁡δ\tan\delta, PD
CablesIR, DC leakage, tan⁡δ\tan\delta, PD (with location)
TransformersIR and PI, tan⁡δ\tan\delta, PD, DGA, oil BDV
Rotating machinesIR, PI, tan⁡δ\tan\delta tip-up, PD
Insulating oilBDV, moisture, tan⁡δ\tan\delta, resistivity