General HV tests; resistance divider with micro-ammeter

Short answer

General tests: sustained low-frequency (withstand/flashover), DC, high-frequency, and impulse (lightning/switching) tests. Measurement: series resistor with micro-ammeter reads V=IR; micro-ammeter at earth potential, protected by gap. Alternatively, a resistive divider (R1, R2) yields V = V2*(R1+R2)/R2, measured by a high-impedance voltmeter.

What are the general tests that are carried out on high voltage equipment? Explain with clean circuit diagram the method of measurement of high voltage using resistance divider and micro-ammeter.

General tests on high voltage equipment

High voltage equipment is tested to prove that its insulation can withstand the stresses it will meet in service. By their nature, the general tests are:

  1. Sustained low-frequency (power-frequency) tests – withstand and flashover tests at 50/60 Hz, dry and wet (rain), usually for 1 minute; done on insulators, bushings, transformers, switchgear, cables.
  2. High-voltage DC tests – for cables, capacitors and rotating machines, where AC testing would need very large charging current; also leakage current measurement.
  3. High-frequency tests – at kHz frequencies, for insulators used with carrier/radio frequencies and to check behaviour under high-frequency transients.
  4. Surge or impulse tests – lightning impulse (1.2/50 μs), switching impulse (250/2500 μs) and chopped wave tests, to prove the basic insulation level (BIL/BSL).

By purpose, tests are grouped as type tests (on one design sample), routine tests (on every unit), sample/acceptance tests, and non-destructive tests (insulation resistance, tan⁡δ\tan\delta, capacitance, partial discharge measurement) that check condition without damaging the insulation.

Measurement using series resistance micro-ammeter

A very high resistance RR is connected in series with a micro-ammeter between the high voltage terminal and earth. The current is proportional to the voltage:

V=I RV = I\,R
  HV (V)
    |
   [R]  very high R, in oil/SF6 tube
    |
  ( uA )----+
    |       |  protective gap
    |      ===  or zener
    |       |
  earth ----+
  • RR is built from many wire-wound or metal-film resistors in series, inside an insulating tube filled with oil or SF₆, with corona-free end caps. It is chosen to pass a small current (a few μA to about 1 mA at full voltage).
  • The micro-ammeter is at earth potential, so it can be read safely; it is calibrated directly in kV.
  • A protective device (paper spark gap, neon tube or zener diode) across the meter bypasses the current if RR flashes over.
  • Used mainly for DC; also for AC when the resistor's stray capacitance is small.

Measurement using resistance potential divider

  HV (V) ---+
            |
           [R1]   high-voltage arm
            |
            +-------> V2 (to electrostatic
            |              voltmeter / CRO)
           [R2]   low-voltage arm
            |
  earth ----+
V=V2 R1+R2R2V = V_2\,\frac{R_1 + R_2}{R_2}

The low-voltage output V2V_2 is read by a high-impedance meter (electrostatic voltmeter, digital voltmeter or CRO). For impulses the divider is connected by a matched coaxial cable to an oscilloscope.

Sources of error and remedies

Source of errorRemedy
Heating changes RRLow-temperature-coefficient resistors, low current, oil cooling
Stray capacitance to earthShielding / guard rings around the resistor column
Corona and leakage currentsSmooth end caps, enclosure in oil or SF₆
Resistor inductanceNon-inductive (bifilar) winding
Meter damage on flashoverProtective gap or zener across meter

Accuracy of about ±0.2% to ±2% is obtained with careful construction.