Types of HV tests; sphere gap measurement
Short answer
Tests include type, routine, sample and by voltage: power-frequency, DC, high-frequency, impulse. A sphere gap of diameter D and spacing S measures peak voltage: flashover occurs at a known value from IEC tables, corrected with air density factor δ = 0.386b/(273+t). Used for AC, DC, impulse.
What are the types of tests carried out on high voltage equipment? Explain with neat and clean circuit diagram the method of measurement of high voltage using sphere gaps.
Types of tests on high voltage equipment
- By purpose: type tests (on one sample of a design), routine tests (on every unit), sample/acceptance tests, and special tests.
- By voltage: power-frequency withstand and flashover tests (dry and wet), DC tests, high-frequency tests, and impulse tests (lightning 1.2/50 μs and switching 250/2500 μs); plus non-destructive tests such as and partial discharge.
Measurement of high voltage using sphere gaps
A sphere gap consists of two identical polished metal spheres separated by an air gap. The uniform field between spheres gives a breakdown voltage that is accurately known (IEC 60052 / IEEE Std 4 tables) for a given sphere diameter and spacing . By noting the spacing at which flashover occurs, the peak value of AC, DC or impulse voltage is found.
HV test R (series
source ----/\/\/\----+
(AC/DC/ |
impulse) ( HV ) upper sphere
| | S gap spacing
| ( E ) lower sphere
| | (earthed)
+-------earth---+
Construction and arrangement
- Two equal spheres of copper, brass or aluminium, of standard diameters (2, 5, 6.25, 10, 12.5, 15, 25, 50, 75, 100, 150, 200 cm).
- Small spheres are mounted horizontally; large spheres (about 50 cm and above) vertically with the lower sphere earthed.
- Shafts, supports and nearby objects must keep the clearances given in the standard so that the field is not disturbed.
- A series resistor limits the current at flashover, protects the sphere surfaces from pitting and damps oscillations: about 100 kΩ to 1 MΩ for AC and DC; a low, non-inductive value (below about 500 Ω) for impulses so the wave is not distorted.
Procedure
- Set the spacing larger than expected; apply the voltage.
- For AC/DC, raise the voltage slowly (or reduce the gap) until flashover occurs; repeat several times and take the mean.
- For impulses, find the 50% flashover voltage: the spacing at which half of the applied impulses cause flashover.
- Read the standard breakdown voltage (kV peak) for that and from the table.
Correction for air density
Tables are for 20 °C and 760 mm Hg. Relative air density
( in mm Hg, in °C). The actual breakdown voltage is , where is a correction factor; for , .
Factors affecting accuracy
- Spacing should not exceed for ±3% accuracy (up to with lower accuracy).
- Nearby earthed objects and the shaft affect the field.
- Dust, fibres and humidity cause erratic flashovers; spheres must be clean and smooth.
- For gaps below about 1 cm (and impulse tests) the gap is irradiated with UV light or a radioactive source to provide initiating electrons and reduce scatter.
Advantages: measures peak of AC, DC and impulse voltages; simple, rugged; used to calibrate other instruments. Limitations: the measuring process causes flashover, so it cannot monitor voltage continuously, and corrections are needed.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- General tests on high voltage equipment · High Voltage Engineering, chapter 7
- General HV tests; resistance divider with micro-ammeter · High Voltage Engineering, chapter 7 · asked 3×
- General HV tests and electrostatic voltmeter · High Voltage Engineering, chapter 7
- High voltage measurement by electrostatic voltmeter · High Voltage Engineering, chapter 7 · asked 2×
- HV AC measurement methods and electrostatic voltmeter · High Voltage Engineering, chapter 7 · asked 2×
- Voltage sharing between air gap and press board · High Voltage Engineering, chapter 6
- 8 kVA 400/120 V tests, parameters on HV side · Electrical Machines, chapter 2
- Measurement parameters and high VSWR measurement · RF and Microwave Engineering, chapter 8
- Bridge for high-Q inductance measurement · Instrumentation I, chapter 2
- Time measurement circuit · Digital Logic, chapter 11 · asked 4×