The bus admittance matrix Ybus relates injected currents I = Ybus V. Diagonal element Yii is the sum of all admittances connected to bus i; off-diagonal Yik equals negative of the series admittance between buses i and k, zero if no connection.

What is a bus admittance matrix? Define its elements.

The bus admittance matrix YbusY_{bus} is an n×nn \times n matrix that relates the currents injected at the nn buses of a power network to the bus voltages measured from the reference (ground):

Ibus=Ybus Vbus,Ii=∑k=1nYikVk\mathbf{I}_{bus} = \mathbf{Y}_{bus}\,\mathbf{V}_{bus},\qquad I_i = \sum_{k=1}^{n} Y_{ik}V_k

For a 3-bus system:

[I1I2I3]=[Y11Y12Y13Y21Y22Y23Y31Y32Y33][V1V2V3]\begin{bmatrix} I_1 \\ I_2 \\ I_3 \end{bmatrix} = \begin{bmatrix} Y_{11} & Y_{12} & Y_{13} \\ Y_{21} & Y_{22} & Y_{23} \\ Y_{31} & Y_{32} & Y_{33} \end{bmatrix} \begin{bmatrix} V_1 \\ V_2 \\ V_3 \end{bmatrix}

Diagonal elements: self (driving-point) admittance

Yii=yi0+∑k≠iyik=IiVi∣Vk=0, k≠iY_{ii} = y_{i0} + \sum_{k \ne i} y_{ik} = \left.\frac{I_i}{V_i}\right|_{V_k = 0,\ k \ne i}

YiiY_{ii} is the sum of all admittances connected to bus ii, including series line admittances and shunt elements (half line charging, capacitors, reactors). It equals the current injected at bus ii per unit voltage at bus ii when all other buses are shorted to ground.

Off-diagonal elements: mutual (transfer) admittance

Yik=−yik=IiVk∣Vj=0, j≠kY_{ik} = -y_{ik} = \left.\frac{I_i}{V_k}\right|_{V_j = 0,\ j \ne k}

YikY_{ik} is the negative of the series admittance between buses ii and kk. It is the current injected at bus ii per unit voltage applied at bus kk with all other buses shorted. If buses ii and kk are not directly connected, Yik=0Y_{ik} = 0.

Properties

  • Symmetric: Yik=YkiY_{ik} = Y_{ki} (no phase-shifting transformers).
  • Sparse: most off-diagonal elements are zero in large networks.
  • Usually diagonally dominant, since YiiY_{ii} is the sum of the admittances that appear (with opposite sign) in the off-diagonal terms of its row; it is formed easily by inspection.
  • Used directly in Gauss–Seidel and Newton–Raphson load flow.

✓ Answer checked by Claude Sonnet 5.5