Short answer

Buses are slack (known |V|, δ; unknown P, Q), PV (known P, |V|; unknown Q, δ), or PQ (known P, Q; unknown |V|, δ). For a four-bus system, Ybus diagonal elements are sum of admittances at each bus, off-diagonals are negative mutual admittances, and zero if no direct connection.

Explain bus classification in power flow analysis with their known and unknown quantities and hence formulate the bus admittance matrix for four bus system.

In load-flow analysis each bus has four quantities: PP, QQ, ∣V∣|V| and δ\delta. Two are specified and two are found by the solution. Buses are classified according to which two are known.

Bus classification

Bus typeKnownUnknownExample
Slack / swing / reference bus∣V∣\lvert V\rvert, δ\delta (usually δ=0\delta = 0)PP, QQLargest generating station
PV / generator / voltage-controlled busPP, ∣V∣\lvert V\rvert (with QminQ_{min}, QmaxQ_{max})QQ, δ\deltaGenerator buses, buses with SVC
PQ / load busPP, QQ∣V∣\lvert V\rvert, δ\deltaLoad buses (about 80% of buses)
  • Slack bus: only one in the system. Its P and Q make up the difference between scheduled generation and load + losses (losses are unknown before the solution). Its voltage angle serves as reference.
  • PV bus: real power output is set by the turbine and voltage magnitude by the AVR. If the computed Q exceeds its limits, Q is fixed at the limit and the bus becomes a PQ bus.
  • PQ bus: net injection P=PG−PDP = P_G - P_D, Q=QG−QDQ = Q_G - Q_D is known; voltage is found.

Ybus for a four-bus system

Take a four-bus network with lines 1-2, 1-3, 2-3, 2-4 and 3-4. Each line has series admittance yiky_{ik} and shunt yik′/2y'_{ik}/2 at each end; total shunt at bus ii is yi0y_{i0}.

Applying KCL:

I1=y10V1+y12(V1−V2)+y13(V1−V3)I2=y20V2+y12(V2−V1)+y23(V2−V3)+y24(V2−V4)I3=y30V3+y13(V3−V1)+y23(V3−V2)+y34(V3−V4)I4=y40V4+y24(V4−V2)+y34(V4−V3)\begin{aligned} I_1 &= y_{10}V_1 + y_{12}(V_1 - V_2) + y_{13}(V_1 - V_3) \\ I_2 &= y_{20}V_2 + y_{12}(V_2 - V_1) + y_{23}(V_2 - V_3) + y_{24}(V_2 - V_4) \\ I_3 &= y_{30}V_3 + y_{13}(V_3 - V_1) + y_{23}(V_3 - V_2) + y_{34}(V_3 - V_4) \\ I_4 &= y_{40}V_4 + y_{24}(V_4 - V_2) + y_{34}(V_4 - V_3) \end{aligned} Ybus=[y10+y12+y13−y12−y130−y12y20+y12+y23+y24−y23−y24−y13−y23y30+y13+y23+y34−y340−y24−y34y40+y24+y34]\mathbf{Y}_{bus} = \begin{bmatrix} y_{10} + y_{12} + y_{13} & -y_{12} & -y_{13} & 0 \\ -y_{12} & y_{20} + y_{12} + y_{23} + y_{24} & -y_{23} & -y_{24} \\ -y_{13} & -y_{23} & y_{30} + y_{13} + y_{23} + y_{34} & -y_{34} \\ 0 & -y_{24} & -y_{34} & y_{40} + y_{24} + y_{34} \end{bmatrix}

General rule: Yii=yi0+∑k≠iyikY_{ii} = y_{i0} + \sum_{k\ne i} y_{ik} and Yik=−yikY_{ik} = -y_{ik} (=0= 0 if no line, e.g. Y14Y_{14}).

These elements are then used in the power-flow equations

Pi−jQi=Vi∗∑k=14YikVkP_i - jQ_i = V_i^*\sum_{k=1}^{4} Y_{ik}V_k

which are solved for the unknowns listed in the table above.