Air flow through openings numerical (0.36 m, 0.4 m)
Short answer
Effective area A = (A1*A2)/√(A1²+A2²) = 0.1007 m². Airflow Q = E*A*V = 0.32*0.1007*1.389 = 0.0448 m³/s (161.1 m³/h).
Calculate the rate of air flow through two square openings of size 0.36 m and 0.4 m in a 4m × 4m × 4m room, with a wind of 5km/hr blowing inclined at 45° to the opening. Take coefficient of effectiveness = 0.32.
Given
- Inlet and outlet openings: 0.36 m × 0.36 m and 0.4 m × 0.4 m, so and
- Wind speed km/h m/s, at 45° to the opening
- Coefficient of effectiveness (already accounts for the wind direction; the room size does not enter the formula)
Formula
For wind-driven ventilation through two openings in series, the effective area is
Calculation
Answer: m³/s m³/h.