- 2070 Bhadra · 8 marks
Circular Sal column, open shed, 200 kN
Short answer
Provide a circular Sal column of diameter 180 mm. Equivalent square side = 159.5 mm, S/a = 21.94 (long), fc = 8.66 N/mm², capacity = 220 kN > 200 kN.
Design a circular salwood column to be used in an open shed, to carry an axial load of 200 kN. The column is 3.5 m high.
Approach. IS 883:1994 cl. 7.6.1.6: the permissible load on a circular column must not exceed that of a square column of equal cross-sectional area. So the circular column is designed through its equivalent square side , with , i.e. .
Data and permissible stresses
Height (unsupported length) m, axial load kN, pin ends.
Species: Sal (Shorea robusta), Group A. Location: outside. Grade: Grade I (standard) (Table 1 values are for Grade I).
Permissible stresses (IS 883:1994 Table 1, outside location):
| Property | Table 1 value (N/mm²) | Used (N/mm²) |
|---|---|---|
| Bending / tension along grain | 14.0 | 14.00 |
| Compression parallel to grain | 9.4 | 9.40 |
| Compression perpendicular to grain | 3.5 | 3.50 |
| Horizontal shear | 0.94 | 0.94 |
| Modulus of elasticity | 12670 | 12670 |
An open shed is an outside location; the grade is not stated, so Grade I is used.
Trial section
Try diameter mm. Area mm². Equivalent square side:
Slenderness and permissible stress
, so it is a long column (, OK):
Check
Safe.
Answer: provide a circular Sal column of diameter 180 mm. (Its permissible load equals that of a 160 mm square column of the same area.)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Square deodar column 4 m, 250 kN, open shed · Design of Steel and Timber Structure, chapter 11
- Select Sal column, 200 kN + 30 kNm · Design of Steel and Timber Structure, chapter 11
- Check 25 cm x 25 cm Sal column, 200 kN + 20 kNm · Design of Steel and Timber Structure, chapter 11
- Built-up Sal column, 50x250 planks, 925 kN · Design of Steel and Timber Structure, chapter 11 · asked 2×
- Sal timber column, 50 kN, 4 m · Design of Steel and Timber Structure, chapter 11
- Solid Sal column, 75 kN + 12 kNm, 2 m · Design of Steel and Timber Structure, chapter 11
- Brick column design for 80 kN axial load · Concrete Technology and Masonry Structure, chapter 8
- Timber column under axial load and bending · Design of Timber and Masonry Structures, chapter 3
- Safe axial load on a timber column · Design of Timber and Masonry Structures, chapter 3
- Corner stresses of 400 x 800 column (200 kN) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
All Design of Steel and Timber Structure chapter 11 questions →