Brick column design for 80 kN axial load
Short answer
Trial sections checked for slenderness and stress. Adopt a 400 mm × 400 mm column using bricks of minimum crushing strength7.5 N/mm² in cement mortar1∶5 (M1). The permissible stress is0.710 N/mm² against actual0.567 N/mm².
Design a brick column using locally available bricks to carry an axial load of 80 kN from a roof consisting of RCC beams and slabs. The height of the brick column is 3.5 m. Take size of brick 200 100 100 mm.
Data and assumptions
- Brick mm (height/width , so from Table 10). Load 80 kN axial, height 3.5 m. RCC beams and slab give lateral support in both directions, so the effective height is the actual height m (IS 1905 cl. 4.3.2, Note 2).
- Column in cement mortar; self weight added (19 kN/m). Maximum slenderness ratio 12 (Table 7).
Step 1: Trial sections
For each size: , (A < 0.2 m), from Table 9 (), self weight, , and the unit strength needed so that ( taken at the unit strength):
| Section (mm) | SR | (kN) | (N/mm²) | Min. unit strength (N/mm²) for each mortar | ||
|---|---|---|---|---|---|---|
| 300 300 | 11.67 | 0.835 | 0.848 | 86.0 | 0.955 | M2: 30; M1: 25; H2: 20; H1: 17.5 |
| 400 400 | 8.75 | 0.940 | 0.927 | 90.6 | 0.566 | M2: 10; M1: 7.5; H2: 7.5; H1: 7.5 |
A 300 mm square column needs very strong bricks (17.5 N/mm or more), so it is not practical for locally made bricks.
Step 2: Adopt 400 mm 400 mm column
For 7.5 N/mm bricks in 1:5 mortar (M1): , :
(5 N/mm bricks give only 0.523 N/mm, not enough.)
Answer: provide a 400 mm 400 mm brick column (two bricks by two bricks) built with bricks of crushing strength not less than 7.5 N/mm in cement mortar 1:5 (M1), with all courses broken-bonded and the column tied to the RCC beam above. Allowable stress 0.710 N/mm against actual 0.567 N/mm.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Brick and mortar for 230 mm wall (100 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Brick and mortar for 250 mm wall (350 kN/m) · Concrete Technology and Masonry Structure, chapter 8 · asked 7×
- Brick column 35 cm x 50 cm allowable load · Concrete Technology and Masonry Structure, chapter 8
- Cross wall design, 125 mm slab, 3.2 m · Concrete Technology and Masonry Structure, chapter 8 · asked 3×
- Allowable load on 30 x 60 cm column · Concrete Technology and Masonry Structure, chapter 8
- Interior cross wall design: three-storey, 150 mm slab · Concrete Technology and Masonry Structure, chapter 8 · asked 2×
- Timber column under axial load and bending · Design of Timber and Masonry Structures, chapter 3
- Square column with 80 mm eccentricity · Design of RCC Structure, chapter 10
- Safe axial load on a timber column · Design of Timber and Masonry Structures, chapter 3
- Circular Sal column, open shed, 200 kN · Design of Steel and Timber Structure, chapter 11
All Concrete Technology and Masonry Structure chapter 8 questions →