Energy saving calculation: lighting and motor
Short answer
Lighting: replace 100 × (44 W – 18 W) × 3000 h = 7800 kWh/yr saved, Rs 93,600/yr, payback 0.69 years (8.3 months) for Rs 65,000 investment. Motor: old input 12 kW/0.88 =13.64 kW, new 12/0.93=12.90 kW, saving 0.733 kW × 6000 h = 4399 kWh/yr, Rs 52,786/yr, payback 3.03 years. Combined saving: 12,199 kWh/yr, Rs 146,386/yr, total investment Rs 225,000, payback 1.54 years.
An audit of a small factory finds (i) 100 fluorescent tube fittings of 36 W tubes with 8 W ballast loss each, operating 10 h/day for 300 days a year; (ii) a 15 kW, 88 % efficient motor loaded at 80 % and running 6000 h/year. The tariff is Rs 12 per kWh. Replacing each fitting with an 18 W LED lamp (cost Rs 650 each, no ballast) and the motor with a 93 % efficient energy-efficient motor (cost Rs 160 000) are proposed. Calculate the annual energy and money savings and the simple payback period for each measure and the combined measure.
(i) Lighting retrofit
Existing load per fitting W; proposed W.
Investment .
(ii) Motor replacement
Shaft output kW.
Combined
Answer: lighting saves 7800 kWh (Rs 93 600), payback 8.3 months; motor saves 4399 kWh (Rs 52 786), payback 3.0 years; combined 12 199 kWh (Rs 146 386) per year, payback 1.54 years (about 18 months). The lighting measure should be done first.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Energy audit types and audit procedure · Energy Resources, chapter 9
- Energy audit instruments and energy balance · Energy Resources, chapter 9
- Preparing and presenting an energy audit report · Energy Resources, chapter 9
- Wind turbine power, tip speed ratio and energy · Energy Resources, chapter 4
- Energy and cost saving from lighting retrofit · Industrial Power Distribution and Illumination, chapter 10
- Electronic ballast replacement savings with ToD tariff · Industrial Power Distribution and Illumination, chapter 10
- EVA; 10 days, 100,000, day 6, spi and cpi · Project Engineering, chapter 4
- Energy loss of 100 kVA transformer in third year · Transmission and Distribution System Design, chapter 7