Energy loss of 100 kVA transformer in third year
Short answer
Third-year load 95 kVA, LF=0.8 gives LLF=0.688. Peak copper loss = 1100×(95/100)² = 992.75 W. Core loss = 200×8760 = 1752 kWh; copper loss = 992.75×0.688×8760 ≈ 5983 kWh. Total annual energy loss ≈ 7735 kWh.
A 3-phase transformer of 100 kVA supplies a load of 75 kVA in its first year of installation and addition 10 kVA for subsequent two years. Calculate the energy loss for third year with following parameters given: Voltage level = 11/0.4 kV, Frequency = 50 Hz, Load Factor = 0.8, No load losses = 200 W, Copper loss = 1100 W, Loss of load factor = 0.3×LF + 0.7×(LF)².
Energy loss = core loss for all hours + copper loss at peak × loss of load factor × hours.
Assumptions: "additional 10 kVA for subsequent two years" means the load is 85 kVA in year 2 and 95 kVA in year 3. The given copper loss (1100 W) is at rated load (100 kVA). The year has 8760 h.
Step 1: Third-year peak load
Step 2: Loss of load factor
Step 3: Copper loss at 95 kVA
Step 4: Annual energy losses
Answer: Energy loss in the third year ≈ 7735 kWh (copper 5983 kWh + core 1752 kWh).
Because the load factor is high (0.8) and the transformer is loaded at 95%, copper loss is the dominant part of the energy loss.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Monthly energy loss of 50 kVA transformer · Transmission and Distribution System Design, chapter 7
- Power loss, 10 km 11 kV UDL feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Percentage energy loss of 25 kVA transformer · Transmission and Distribution System Design, chapter 7
- Loss and drop, 15 km 11 kV feeder · Transmission and Distribution System Design, chapter 7 · asked 2×
- Loss and voltage drop, 16 km uniformly varying load · Transmission and Distribution System Design, chapter 7
- Monthly energy loss in four secondary lines · Transmission and Distribution System Design, chapter 7
- Design: 100 kVA 11/132 kV transformer with winding data · Electric Machine Design, chapter 3 · asked 3×
- Design: 500 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 6×
- Design: 4000 kVA 66/11 kV power transformer · Electric Machine Design, chapter 3 · asked 5×
- Design data: 1000 kVA 66/11 kV transformer · Electric Machine Design, chapter 3
All Transmission and Distribution System Design chapter 7 questions →