Percentage energy loss of 25 kVA transformer

Short answer

Load factor = 4800/(20×720) = 0.333, LLF = 0.1778. Peak copper loss = 300×(23.53/25)² = 265.7 W. Monthly core loss 51.84 kWh, copper loss 34.02 kWh. Total loss 85.86 kWh gives percentage loss = 85.86/4800×100 ≈ 1.79%.

A distribution transformer of 25 kVA with no-load loss of 72 W and rated copper loss is 300 W. Consider the demand for the transformer is 20 kW and the monthly energy sell equals 4800 units @ 0.85 power factors. Use Loss of Load Factor (LLF) = 0.3LF + 0.7LF². Find the percentage energy loss.

Percentage energy loss = (core energy loss + copper energy loss) / energy sold × 100. Copper energy loss uses the loss of load factor.

Assumption: month = 30 days = 720 h.

Step 1: Load factor

LF=EnergyPmax×T=480020×720=0.3333LF = \frac{\text{Energy}}{P_{max} \times T} = \frac{4800}{20 \times 720} = 0.3333

Step 2: Loss of load factor

LLF=0.3 LF+0.7 LF2=0.3(0.3333)+0.7(0.3333)2=0.1000+0.0778=0.17778\begin{aligned} LLF &= 0.3\,LF + 0.7\,LF^2 \\ &= 0.3(0.3333) + 0.7(0.3333)^2 \\ &= 0.1000 + 0.0778 = 0.17778 \end{aligned}

Step 3: Copper loss at peak load

Speak=200.85=23.529 kVAPcu,peak=300×(23.52925)2=300×0.8858=265.74 W\begin{aligned} S_{peak} &= \frac{20}{0.85} = 23.529 \text{ kVA} \\ P_{cu,peak} &= 300 \times \left(\frac{23.529}{25}\right)^2 = 300 \times 0.8858 = 265.74 \text{ W} \end{aligned}

Step 4: Monthly energy losses

Ecu=0.26574×0.17778×720=34.02 kWhEcore=0.072×720=51.84 kWhEloss=34.02+51.84=85.86 kWh\begin{aligned} E_{cu} &= 0.26574 \times 0.17778 \times 720 = 34.02 \text{ kWh} \\ E_{core} &= 0.072 \times 720 = 51.84 \text{ kWh} \\ E_{loss} &= 34.02 + 51.84 = 85.86 \text{ kWh} \end{aligned}

Step 5: Percentage energy loss

%Eloss=85.864800×100=1.79%\%E_{loss} = \frac{85.86}{4800} \times 100 = 1.79\%

(Based on energy input 4800+85.86=4885.864800 + 85.86 = 4885.86 kWh, it is 85.86/4885.86=1.76%85.86/4885.86 = 1.76\%.)

Answer: Percentage energy loss ≈ 1.79% of energy sold (monthly loss ≈ 85.9 kWh: 51.84 kWh core loss + 34.02 kWh copper loss).

Note that core loss is the larger part, because the load factor is low (0.33): the transformer is energised all month but carries peak load only briefly.