- 2071 Magh · 4 marks
Coefficient of utilization and its factors
What is the coefficient of utilization and explain the factors should be considered while selecting the above.
The coefficient of utilization (CU) or utilisation factor is the ratio of the lumens that actually reach the working plane to the total lumens emitted by the lamps:
CU = lumens received on the working plane / total lumens emitted by the lamps
It is always less than 1 (typically 0.4–0.8), because some light is absorbed by the luminaire, walls and ceiling or falls outside the working plane. It is used in the lumen method: N = E × A / (φ × CU × MF).
Factors considered while selecting CU
- Type of luminaire and light distribution: direct luminaires send most light downward and give a high CU; indirect lighting depends on ceiling reflection and gives a low CU. Luminaire efficiency (light output ratio) also matters.
- Room index (room dimensions and mounting height): RI = L × W / [Hm (L + W)]. Large, low rooms (high RI) give high CU; narrow, tall rooms lose more light on walls (low CU).
- Reflection factors of ceiling, walls and floor: light-coloured, brightly painted surfaces reflect more light back and raise CU; dark surfaces lower it.
- Mounting height: higher mounting spreads more light onto walls, lowering CU.
- Colour and condition of surroundings and obstructions: machinery and partitions block light.
CU is read from manufacturers' tables for the chosen luminaire, entering with room index and reflectances.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Factors in power and lighting system design · Industrial Power Distribution and Illumination, chapter 5
- Conductor sizing factors and armoured cable · Industrial Power Distribution and Illumination, chapter 3
- Power vs lighting system and cable sizing factors · Industrial Power Distribution and Illumination, chapter 5
- Ten factors for flood, street lighting, luminaires · Industrial Power Distribution and Illumination, chapter 8
- Selecting distribution transformer size using Ku and Ks · Industrial Power Distribution and Illumination, chapter 4 · asked 3×
- Distribution substation site selection factors · Industrial Power Distribution and Illumination, chapter 4
- Factors for selecting roof covering · Building Technology, chapter 4 · asked 2×
- Factors for selecting construction materials · Civil Engineering Materials, chapter 1 · asked 9×
- Factors in selecting construction equipment · Construction Management, chapter 4 · asked 6×
- Factors for selecting a motor · Utilization of Electrical Energy, chapter 2 · asked 2×
All Industrial Power Distribution and Illumination chapter 7 questions →