Conductor sizing factors and armoured cable
Short answer
Conductor size is chosen for load current, derated for installation conditions, and must satisfy voltage drop within 2.5–5% and short-circuit withstand (A ≥ I_sc·√t/k). Additional factors: load type, future expansion, economy, and mechanical strength. A 3.5-core armoured cable has three full-size phase conductors and a reduced neutral (half size), each stranded Cu/Al with PVC/XLPE insulation, fillers, inner bedding, galvanized steel wire/strip armour, and outer PVC sheath.
Point out factors to be considered while determining the sizes of conductor. Explain construction features of 3.5 core armoured cable.
The conductor size of a cable is chosen so that it carries the load current without overheating, keeps the voltage drop within limits and survives the short-circuit current until the protection clears the fault.
Factors for deciding conductor size
- Load (design) current: I = P / (√3 · V_L · cosφ · η) for 3-phase loads; the cable rating must be ≥ the design current and ≥ the rating of the protective device.
- Derating factors: ambient temperature, grouping of cables, depth of laying, soil thermal resistivity and method of installation (air, duct, ground) reduce the rating given in the tables.
- Voltage drop: the drop from supply to load should be within the permitted value (about 2.5–5 % of rated voltage). Long cables are often sized by voltage drop, not current.
- Short-circuit withstand: A ≥ I_sc · √t / k, where k depends on conductor and insulation (about 115 for Cu-PVC, 143 for Cu-XLPE).
- Type of load: motor starting current, harmonics (neutral current), duty cycle.
- Future expansion: a margin of about 20–25 %.
- Economy and material: copper vs aluminium, cost of energy losses over the cable life.
- Mechanical strength: minimum sizes (e.g. 1.5 mm² Cu for lighting, 2.5 mm² Cu for power sockets).
Construction of 3½-core armoured cable
A 3½-core cable has three full-size phase conductors and one reduced-size neutral (about half the phase area), used for 3-phase 4-wire LT supply where neutral current is smaller than phase current.
outer PVC sheath
/ steel wire / strip armour
/ / bedding (inner sheath)
/ / / filler
( ( ( ___ ___ ) ) )
( R ) ( Y )
\ /
( B ) (n) <- reduced neutral
each core: conductor + PVC/XLPE insulation
Layers from inside to outside:
- Conductors: stranded copper or aluminium, often sector shaped to reduce the overall diameter; three phase cores plus one half-size neutral.
- Insulation: PVC or XLPE over each conductor, colour coded (red, yellow, blue, black).
- Fillers: non-hygroscopic PVC or polypropylene fillers that make the laid-up cores round.
- Inner sheath (bedding): extruded PVC layer that protects the cores and gives a bed for the armour.
- Armour: galvanised steel wires (round) or steel strips laid helically; gives mechanical protection and acts as an earth-continuity path. Single-core cables use non-magnetic (aluminium) armour.
- Outer sheath (serving): tough PVC (or FRLS) sheath against moisture, chemicals and corrosion, with voltage grade and size printed on it.
Such cables (e.g. 1.1 kV, 3½ × 95 mm² Al XLPE armoured) are laid directly in the ground or on trays between the transformer, MDB and SDBs.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Construction of 3.5 core armoured cable · Industrial Power Distribution and Illumination, chapter 3 · asked 3×
- Power vs lighting system and cable sizing factors · Industrial Power Distribution and Illumination, chapter 5
- Cable classification and 3½ core construction · Industrial Power Distribution and Illumination, chapter 3
- 3.5 core cable for 60 A over 200 m · Industrial Power Distribution and Illumination, chapter 5
- Current carrying capacity of cable · Industrial Power Distribution and Illumination, chapter 3
- Optimum conductor radius for minimum cable stress · Power System Analysis I, chapter 2
- Factors while routing signal traces on PCB · Instrumentation II, chapter 8 · asked 4×
- Factors for selecting construction materials · Civil Engineering Materials, chapter 1 · asked 9×
- Factors in selecting construction equipment · Construction Management, chapter 4 · asked 6×
All Industrial Power Distribution and Illumination chapter 3 questions →