- 2076 Baisakh · 6 marks
Optimum conductor radius for minimum cable stress
Short answer
For a single-core cable, maximum stress is g_max = V/(r ln(R/r)). Setting derivative zero gives ln(R/r)=1, so R/r = e ≈ 2.718. The conductor radius should be r = R/e, yielding minimum stress g_max = V/r.
Derive a relation between the conductor radius and inside sheath radius of a single core cable so that the electric stress at the conductor surface may be minimum.
In a single-core cable, the electric stress is greatest at the conductor surface. For a fixed sheath radius, this maximum stress is lowest when .
Stress in a single-core cable
Let the conductor radius be , the inside radius of the sheath , and the voltage between core and sheath . The charge per metre is . By Gauss's law, the field at radius is:
Integrating from to :
The stress is largest at :
Condition for minimum
With and fixed, is least when the denominator is greatest:
The second derivative, , is negative, so this point is a maximum of and therefore a minimum of .
Result:
The insulation thickness is then .
Practical note
The conductor radius from is often larger than the radius needed to carry the current. In that case a hollow conductor or a larger-diameter (for example aluminium) conductor is used to obtain the optimum radius.
Example
Take kV (core to sheath) and cm. Then cm and kV/cm.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Dielectric stress maximum at conductor surface · Power System Analysis I, chapter 2 · asked 2×
- Inductance of composite-conductor single-phase line · Power System Analysis I, chapter 4
- Cable insulation resistance and capacitance · Power System Analysis I, chapter 2
- 400 kV line with 3-conductor bundles: reactances and VAR · Power System Analysis I, chapter 4 · asked 3×
- Capacitive reactance and charging of 2-conductor bundle line · Power System Analysis I, chapter 4 · asked 2×
- Inductance of 4-conductor bundle line, 6 m spacing · Power System Analysis I, chapter 4 · asked 2×
- Derive Mohr-Coulomb principal stress relation · Soil Mechanics, chapter 10 · asked 4×
- Conductor sizing factors and armoured cable · Industrial Power Distribution and Illumination, chapter 3
- 3.5 core cable for 60 A over 200 m · Industrial Power Distribution and Illumination, chapter 5
- Degree of curvature and radius relation · Surveying II, chapter 6