Short answer

By lumen method, required luminaires N = 75×600/(2160×0.8×0.7)=37.2, rounded to 40 single 36 W FTL, arranged 10×4. Spacing 4 m×3.75 m within 6 m limit, actual illuminance 80.6 lux.

An illumination on the working plane of 75 lux is required in a room 40m × 15m in size. The luminaries are required to be hung 4m above the work bench. Assuming a suitable space height ratio, a utilization factor of 0.8, a lamp efficiency of 60 lumen per watt and maintenance factor is 0.7. Estimate the number and disposition of lamp and switches. Design the sub-circuits, distribution board if supply system is 3 phase 4 wire system and consider 1 × 36 watt FTL with electronic ballast.

Given: room 40 m × 15 m, E = 75 lux, Hm = 4 m, UF = 0.8, MF = 0.7, 1 × 36 W FTL with electronic ballast at 60 lm/W, 3-phase 4-wire supply. Assumptions: suitable space–height ratio 1.5 → maximum spacing 1.5 × 4 = 6 m; pf 0.9 with electronic ballast, ballast loss neglected.

Number of luminaires

Lumen method: N = (E × A) / (φ × UF × MF), where φ is the output of one luminaire.

Area A        = 40 × 15 = 600 m²
φ per luminaire = 36 W × 60 lm/W = 2160 lm
Total lumens  = E × A / (UF × MF)
              = 75 × 600 / (0.8 × 0.7)
              = 80357 lm
N             = 80357 / 2160 = 37.2

Rounding up and fitting a regular grid: 10 × 4 = 40 luminaires (10 along the 40 m side, 4 along the 15 m side).

Arrangement and spacing

Spacing along length = 40/10 = 4 m
Spacing along width  = 15/4 = 3.75 m
End spacing (to wall) = half of these
Max spacing = SHR × Hm = 1.5 × 4 = 6 m
4 m and 3.75 m ≤ 6 m  → OK
Actual E = 40 × 2160 × 0.8 × 0.7 / 600
         = 80.6 lux (≥ 75 lux required)

Layout diagram

Plan 40 m × 15 m (letter = phase of lamp circuit)
+---------------------+
| R R R R R R R Y Y Y |
| B B B B B B Y Y Y Y |
| B R R R R R R R Y Y |
| B B B B B B Y Y Y Y |
+---------------------+
[DB]  [SB]  <- entrance: DB and switch board
       S S S S ... one switch per sub-circuit

Each light sub-circuit is controlled by one 6 A one-way switch; all switches are grouped on a switch board (SB) next to the entrance, and the DB is mounted beside it.

Sub-circuits

Rule (IS 732 / NEA practice): a light sub-circuit carries at most 10 points and 800 W. Here one luminaire is 36 W, so up to 10 luminaires per sub-circuit. Number of circuits is made a multiple of 3 for phase balance.

CircuitLuminairesLoad (W)Current (A)PhaseMCB
L172521.22R6 A
L272521.22Y6 A
L372521.22B6 A
L472521.22R6 A
L562161.04Y6 A
L662161.04B6 A

Distribution board design

PhaseCircuitsLoad (W)Current (A)
RL1, L45042.43
YL2, L54682.26
BL3, L64682.26
Total connected load = 1440 W (lighting)
Most loaded phase    = 504 W
Iph = 504 / (230 × 0.9) = 2.43 A
Main MCB ≥ 1.25 × 2.43 = 3.04 A → 6 A TPN MCB

DB specification: 4-way-per-phase TPN DB (12 ways in all, spares included) with 6 A TPN MCB as incomer, 25 A 4-pole RCCB (100 mA) for earth-leakage protection, 6 A SP MCBs (B-curve) for light circuits. Incoming cable: 4-core 1.5 mm² Cu PVC (rating 21 A ≥ 6 A), plus earth continuity conductor.

3-phase, 400/230 V, 4-wire supply
        |
   [Energy meter]
        |
   [6 A TPN MCB]
        |
   [25 A 4P RCCB]
        |
==R====Y====B====N== busbars
  |    |    |    |    |
  L1   L2   L3   L4   L5  ...