Sewer at 2/3 depth, 0.70 m³/s

Short answer

Full-flow discharge Q_f = 0.70/0.7839 = 0.893 m³/s, giving D = 1.032 m (adopt 1050 mm). At peak flow, velocity is 1.20 m/s, which is below the non-scouring limit of 3 m/s, so safe.

What will be the diameter of a circular concrete sewer carrying 2/3rd depth at the peak discharge of 0.70 m³/s laid in a gradient of 1 in 1000? Also check whether it is safe for non-scouring velocity or not. Assume Manning's 'n' as 0.012.

Given

Peak discharge Q=0.70Q=0.70 m³/s, S=1/1000S=1/1000, n=0.012n=0.012, depth of flow d/D=2/3=0.667d/D=2/3=0.667.

For d/D=0.6667d/D=0.6667: θ=2cos⁡−1(1−2d/D)=218.94∘\theta = 2\cos^{-1}(1-2d/D)=218.94^\circ, A/Af=θ−sin⁡θ2π=0.7082A/A_f=\dfrac{\theta-\sin\theta}{2\pi}=0.7082, R/Rf=1−sin⁡θθ=1.1645R/R_f=1-\dfrac{\sin\theta}{\theta}=1.1645, so v/vf=(R/Rf)2/3=1.1069v/v_f=(R/R_f)^{2/3}=1.1069 and Q/Qf=(A/Af)(v/vf)=0.7839Q/Q_f=(A/A_f)(v/v_f)=0.7839 (n taken constant).

Size of the sewer

Discharge when running full:

Qf=QQ/Qf=0.70000.7839=0.8930 m3/sQ_f=\frac{Q}{Q/Q_f}=\frac{0.7000}{0.7839}=0.8930\ \text{m}^3/\text{s}

Manning's formula for a full circular pipe, Qf=0.3117nD8/3S1/2Q_f=\dfrac{0.3117}{n}D^{8/3}S^{1/2}, with S=0.00100S=0.00100 and n=0.012n=0.012:

D=(Qf n0.3117 S1/2)3/8=(0.8930×0.0120.3117×0.03162)3/8=1.032 mD=\left(\frac{Q_f\,n}{0.3117\,S^{1/2}}\right)^{3/8}=\left(\frac{0.8930\times0.012}{0.3117\times0.03162}\right)^{3/8}=1.032\ \text{m}

Adopt the next standard size, D = 1050 mm.

Check of velocity and capacity

For the adopted pipe: vf=0.3969nD2/3S1/2=1.081v_f=\dfrac{0.3969}{n}D^{2/3}S^{1/2}=1.081 m/s and Qf=0.9355Q_f=0.9355 m³/s.

v=vf×(v/vf)=1.081×1.1069=1.20 m/sQcapacity=Qf×(Q/Qf)=0.9355×0.7839=0.7333 m3/s (≥0.7000)\begin{aligned} v&=v_f\times(v/v_f)=1.081\times1.1069=1.20\ \text{m/s}\\ Q_{capacity}&=Q_f\times(Q/Q_f)=0.9355\times0.7839=0.7333\ \text{m}^3/\text{s}\ (\ge 0.7000) \end{aligned}

The velocity at maximum flow, 1.20 m/s, lies between the minimum (0.6 m/s) and the maximum non-scouring limit (3.0 m/s), so it is satisfactory.

For non-scouring, the velocity must not exceed the maximum permissible value (about 3 m/s for concrete sewers), and for self-cleansing it should be at least 0.6 m/s. The velocity is 1.20 m/s at peak flow, which is within 0.6-3.0 m/s, so the sewer is safe against scouring and also self-cleansing at peak flow. (At lower flows the velocity falls, so flows below about 0.058 m³/s give less than 0.6 m/s, and the minimum flow should be checked separately.)

Answer: D = 1050 mm (computed 1.032 m); v = 1.20 m/s < 3 m/s, so safe.