Short answer

i) Minimum oil CB uses oil, has moderate speed and some fire hazard; air blast CB uses compressed air, is very fast, fire-free, but noisy and needs a compressor. ii) Air blast CB is fast, compact, no fire hazard, but requires an air plant; bulk oil CB is heavy, slow, high fire risk, but simple and needs no auxiliary equipment.

Compare the performance and characteristics of i) minimum oil circuit breaker and air blast CB ii) Air-blast circuit breaker and bulk oil circuit breaker.

The comparison is based on how each breaker quenches the arc and the practical consequences in speed, safety, maintenance and application.

i) Minimum oil CB vs Air blast CB

PointMinimum oil CBAir blast CB
Arc quenching mediumSmall quantity of oil; arc produces hydrogen gasCompressed air at 20–30 bar
Insulation to earthPorcelain/solid materialPorcelain and air
Arc extinctionBy gas bubble and turbulator (cross/axial vent)By air blast cooling and sweeping the arc
Arcing timeLongerVery short
SpeedMediumHigh
Fire riskSmall (some oil present)None
Repeated operation / auto-recloseNot suitableVery suitable
Auxiliary plantNoneCompressor and air receiver
NoiseQuietVery noisy
Current choppingLowSignificant; resistors needed
MaintenanceOil change after a few fault clearancesCompressor and valves
Range3.3–132 kV66–400 kV

ii) Air blast CB vs Bulk oil CB

PointAir blast CBBulk oil CB
MediumCompressed airLarge volume of oil in earthed steel tank
InsulationAir/porcelainOil insulates contacts from tank
Size and weightSmaller, lighter for the same ratingVery heavy and bulky
Fire and explosion hazardNilHigh
Speed of operationFast (2–3 cycles)Slow (5–8 cycles)
Arc energy and contact erosionLowHigh
Medium after operationFresh air every timeOil carbonises, needs filtering
Frequent operationSuitableUnsuitable
NoiseVery highLow
Auxiliary plantCompressor neededNone
CostHigh (with air plant)Low
ApplicationEHV transmission, frequent switchingOld distribution systems, up to 33 kV

Remarks

  • Oil breakers are simple and need no auxiliary plant, but carry fire risk and are slow.
  • Air blast breakers are fast and clean, but costly and noisy; they have largely been replaced by SF6 breakers at EHV.