Compare MOCB/BOCB and ABCB/puffer SF6

Short answer

i) Minimum oil CB uses only quenching oil with solid insulation, is smaller and lower fire risk than bulk oil CB which uses large oil for quenching and insulation; MOCB oil deteriorates faster. ii) Air blast CB uses external compressed air, noisy, high chopping; puffer SF6 CB generates its own SF6 blast, silent, very fast, low maintenance, no exhaust.

Compare the performance and characteristics and working principle of: i) Minimum oil circuit breaker vs Bulk oil circuit breaker ii) Air blast circuit breaker vs puffer type SF6 circuit breaker.

The comparison covers working principle, performance and characteristics of each pair.

i) Minimum oil CB vs Bulk oil CB

Working principle (common): the arc between separating contacts decomposes oil into a gas bubble (mainly hydrogen); high pressure and cooling by hydrogen deionise the gap so that the arc goes out at current zero.

PointMinimum oil CBBulk oil CB
Role of oilArc quenching onlyArc quenching and insulation to earth
TankSmall porcelain chamber, kept liveLarge earthed steel tank
Oil quantityAbout 10% of BOCBVery large
Arc controlTurbulator (axial/side vent) always usedPlain break or explosion pot
Size, weightSmall, lightHeavy, bulky, large foundations
Fire riskLowHigh
Oil deteriorationFast (small volume)Slow
MaintenanceFrequent oil changeOil filtering, tank cleaning
Range3.3–132 kVUp to 33 kV

ii) Air blast CB vs Puffer type SF6 CB

Working principle:

  • ABCB: a blast of compressed air from a separate reservoir is blown on the arc; it cools the arc and sweeps away ions, and air is exhausted to atmosphere.
  • Puffer SF6: the moving contact drives a piston that compresses SF6 in a cylinder and blows it through a nozzle over the arc. SF6 is electronegative and absorbs free electrons, so the gap recovers very fast. Gas stays in a sealed enclosure.
PointAir blast CBPuffer SF6 CB
MediumAir at 20–30 barSF6 at about 5–7 bar
Gas supplyExternal compressor and receiverSelf-generated by piston; no compressor
Dielectric strengthLow (needs high pressure)2.5–3 times air
Arc time constantLargerVery small
Current choppingHigh; resistors neededNegligible
NoiseVery loud exhaustSilent (closed system)
Breaks per pole at EHVMoreFewer
MaintenanceCompressor, valves, leaksVery low; gas leak monitoring
EnvironmentClean (air)SF6 is a strong greenhouse gas
CostHigh (with air plant)Moderate
Present useMostly replacedStandard for 33–765 kV

Remarks

SF6 puffer breakers combine the speed of air blast breakers with silent, compact and low-maintenance operation, which is why they have replaced both oil and air blast types at transmission voltages.

✓ Answer checked by Claude Opus 5.5 (high effort)

All Switchgear and Protection chapter 6 questions →