Vacuum versus SF6 circuit breaker

Short answer

VCB uses vacuum, SF6 uses electronegative gas. VCB is standard for MV (3.3–36 kV) with high operation life and low maintenance; chopping may need surge protection. SF6 dominates HV/EHV (72.5–800 kV), has low chopping, restrike-free capacitive switching, and is used in outdoor switchyards and GIS, but requires gas monitoring and has environmental concerns.

Make a comparison between vacuum circuit breaker with SF6 circuit breaker in a power system.

A vacuum circuit breaker (VCB) extinguishes the arc in a sealed vacuum bottle (about 10−610^{-6} to 10−410^{-4} torr), where the arc is a metal vapour arc that dies at current zero. An SF6 circuit breaker extinguishes the arc by blowing sulphur hexafluoride, an electronegative gas, across it. The gas captures free electrons and quickly restores dielectric strength.

Arc quenching in brief

  • VCB: on contact separation, metal vapour from the contacts carries the arc. At current zero the vapour condenses on shields within microseconds, so the gap recovers very fast. Spiral or axial magnetic field contacts keep the arc diffuse.
  • SF6: puffer or self-blast type. The moving piston compresses the gas and blows it through the nozzle onto the arc. SF6 has about 2–3 times the dielectric strength of air at the same pressure.
 VCB bottle               SF6 puffer interrupter
 +---------+              +-----------------+
 | fixed   |              | fixed contact   |
 |  ===    |              |   ==   <- gas   |
 |  shield |              |  nozzle  blast  |
 |  ===    |              |   ==  piston    |
 | moving  |              | moving contact  |
 +--bellows+              +-----------------+

Comparison

PointVCBSF6 CB
MediumVacuumSF6 gas at 3–6 bar
Voltage range3.3–36 kV (mainly MV)33–800 kV (mainly HV/EHV)
Dielectric recoveryVery fastFast
Current choppingHigher; needs surge suppressorsVery low
Contact travelSmall (10–20 mm)Larger
Operating mechanismSmall spring mechanismLarger spring/hydraulic
MaintenanceAlmost none; sealed for lifeGas pressure monitoring, leak checks
Number of operationsVery high (10,000–30,000)Lower
Fire/explosion riskNoneNone
EnvironmentCleanSF6 is a strong greenhouse gas; arc products toxic
MonitoringVacuum loss hard to detectGas density monitor
Size at MVCompactCompact
Size at HVMany breaks, bulkyCompact, used in GIS
CostLower at MVLower at HV
Capacitor switchingPossible restrikeGood

Use in power systems

  • VCB: the usual choice for MV switchgear (11 kV and 33 kV feeders), generator terminals of small–medium hydro units, motor and capacitor bank switching, and frequent-operation duties.
  • SF6: the usual choice for 132 kV, 220 kV and 400 kV outdoor switchyards and GIS. In Nepal the 132/220 kV substations of NEA use SF6 breakers, while 11/33 kV panels use VCBs.

For new designs, SF6-free alternatives (vacuum interrupter with clean air insulation) are spreading because of the environmental impact of SF6.