Short answer

Both relays set PS=100%. Relay B (200/5 CT) set TDS=0.1, giving 0.22s at its 3000A fault. Relay A graded at 3000A: PSM=10, required 0.72s (0.22+0.5), giving TDS=0.72/2.8=0.26. Actual times: Relay A operates at 0.624s for own 4000A fault and 0.728s for backup at B (margin 0.508s).

Design a time-current graded protection scheme based on two identical IDMT relays at points A and B for the following radial feeder. Select appropriate current tap setting and time dial settings for the relays. Find out actual time of operation of relay at A for fault in its zone and as back up. Relay at A should also back up for faults at protection zone of B. [Figure: Source – relay point A – feeder section – relay point B – feeder – far end C.]

Relay pointCT ratioFault current, A
A300/54000
B200/53000
Far end of feeder at point C–2000

IDMT characteristics (for TDS = 1):

PSM23.658101520
T.op. sec1063.93.152.82.22.2

In a time-graded scheme the relay farthest from the source (B) is set fastest, and relay A behind it is set slower by a discrimination margin for every fault in B's zone, so that A acts as back-up.

Assumptions: relay rated current 5 A; load current is below the CT primary rating, so PS = 100% is used on both relays (pick-up = CT primary current); discrimination margin = 0.5 s (breaker time + relay overshoot + safety); TDS steps of 0.01; the curve between table points is interpolated linearly.

Source ─[A]──── AB ────[B]──── BC ──── C
       300/5           200/5
      4000 A          3000 A        2000 A

Relay B (last relay, set fastest)

PS = 100% → pick-up = 200 A primary
Fault at B (3000 A): PSM = 15 → t = 2.2 s (TDS 1)
Fault at C (2000 A): PSM = 10 → t = 2.8 s (TDS 1)
Choose minimum TDS = 0.1
t_B (fault at B) = 0.1 × 2.2 = 0.22 s
t_B (fault at C) = 0.1 × 2.8 = 0.28 s

Relay A

PS = 100% → pick-up = 300 A primary
Grading point: fault at B, 3000 A
(maximum fault current in B's zone)
PSM_A = 3000/300 = 10 → t = 2.8 s (TDS 1)
Required t_A = 0.22 + 0.5 = 0.72 s
TDS_A = 0.72 / 2.8 = 0.257 → choose 0.26

Actual operating times of relay A (TDS = 0.26)

Fault atCurrentPSM_At (TDS 1)t_ARelay B timeMargin
A (own zone)4000 A13.332.40 s0.624 s––
B (back-up)3000 A10.02.80 s0.728 s0.22 s0.508 s
C (back-up)2000 A6.673.48 s0.906 s0.28 s0.626 s

Interpolations used: PSM 13.33 → 2.8 − (3.33/5)(0.6) = 2.40 s; PSM 6.67 → 3.9 − (1.667/3)(0.75) = 3.483 s.

Settings

RelayCTPSTDS
A300/5100% (5 A)0.26
B200/5100% (5 A)0.10

Answer: relay B: PS 100%, TDS 0.1; relay A: PS 100%, TDS 0.26. Relay A operates in 0.624 s for a fault at A in its own zone; as back-up it operates in 0.728 s for a fault at B and 0.906 s for a fault at C, always at least 0.5 s after relay B.