- 2072 Magh · 7 marks
Time-current grading for relays X, Y, Z
Short answer
Relay Z: pick-up 200 A, PSM=10, TMS=0.1 yields 0.28 s. Relay Y: pick-up 250 A, for fault at Z PSM=8, required 0.78 s → TMS=0.26; own fault 0.572 s. Relay X: pick-up 500 A, for fault at Y required 1.072 s → TMS=0.357; own fault 1.0 s. Grading margin 0.5 s.
IDMT characteristics of the relay are shown in figure below. Design the time-current grading of the system as given below. TSM at the relay Z is 0.1. Time setting multiplier is 1. [Figure: Source – relay X – relay Y – relay Z along a radial feeder.]
| Relay Point | C.T. ratio | Fault current | Current Setting |
|---|---|---|---|
| X | 400/5 | 5000 A | 125% |
| Y | 200/5 | 4000 A | 125% |
| Z | 200/5 | 2000 A | 100% |
IDMT Characteristic:
| PSM | 2 | 4 | 6 | 8 | 10 | 12 | 14 | 16 | 18 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|
| Time in sec | 8 | 4 | 3.6 | 3 | 2.8 | 2.6 | 2.4 | 2.2 | 2 | 2 |
Time-current grading means setting each IDMT relay so that the relay nearest the fault trips first, and every relay towards the source waits one grading margin longer.
Assumptions: the given curve is for TMS = 1; the TMS of relay Z is 0.1; grading margin between adjacent relays = 0.5 s (CB time + relay overshoot + errors); CT secondary = 5 A; linear reading of the curve between points.
Formulas
Pick-up current (primary) = Current setting × CT primary
PSM = Fault current / Pick-up current
t = TMS × t(TMS=1, read from curve)
Relay Z (farthest from source)
Pick-up = 1.00 × 200 = 200 A
PSM = 2000 / 200 = 10 → t(TMS=1) = 2.8 s
t_Z = 0.1 × 2.8 = 0.28 s
Relay Y (back-up for Z)
For a fault at Z (2000 A), Y must wait 0.5 s longer than Z.
Pick-up = 1.25 × 200 = 250 A
PSM (fault at Z) = 2000 / 250 = 8 → 3.0 s
Required t_Y = 0.28 + 0.5 = 0.78 s
TMS_Y = 0.78 / 3.0 = 0.26
Fault at Y (4000 A): PSM = 4000/250 = 16 → 2.2 s
t_Y = 0.26 × 2.2 = 0.572 s
Relay X (back-up for Y)
Pick-up = 1.25 × 400 = 500 A
PSM (fault at Y) = 4000 / 500 = 8 → 3.0 s
Required t_X = 0.572 + 0.5 = 1.072 s
TMS_X = 1.072 / 3.0 = 0.357
Fault at X (5000 A): PSM = 5000/500 = 10 → 2.8 s
t_X = 0.357 × 2.8 = 1.0 s
Grading summary
| Relay | Pick-up (A) | TMS | Own-fault PSM | Own-fault time |
|---|---|---|---|---|
| Z | 200 | 0.10 | 10 | 0.28 s |
| Y | 250 | 0.26 | 16 | 0.572 s |
| X | 500 | 0.357 | 10 | 1.00 s |
Source ──X──────Y──────Z────── load
time: 1.0 s 0.57 s 0.28 s (own-fault times)
For the same fault, each relay is 0.5 s slower
than the next relay downstream.
Answer: TMS_Z = 0.1, TMS_Y = 0.26, TMS_X ≈ 0.357 (set 0.36); the operating times for faults at their own points are 0.28 s, 0.572 s and ≈ 1.0 s. A fault at Z is cleared by Z in 0.28 s; Y would back it up at 0.78 s and X later still, so discrimination is achieved.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- IDMT settings for sectionalised radial feeder A, B, C · Switchgear and Protection, chapter 7
- Design IDMT grading for relays A and B · Switchgear and Protection, chapter 7
- IDMT settings for 20 MVA transformer and feeder · Switchgear and Protection, chapter 7 · asked 2×
- IDMT grading: R1, R2 with 1000/5 CTs · Switchgear and Protection, chapter 7 · asked 2×
- IDMT relays across 132/11 kV transformer (3500 A) · Switchgear and Protection, chapter 7
- IDMT relays across 132/33 kV transformer (2000 A) · Switchgear and Protection, chapter 7
- Design: 125 kVA 6600/400 V three phase transformer · Electric Machine Design, chapter 3 · asked 4×
- Fault current: two 50 MVA generators, feeder reactor · Power Plant Equipment, chapter 4 · asked 3×