Short note: Drop-out fuse
Short answer
A drop-out fuse is an outdoor expulsion fuse used on 11–33kV lines. It has a porcelain insulator and a fiberglass tube with a fuse link; on fault, the link melts, arc-extinguishing gases expel the arc, and the tube drops down, providing visible isolation. It is cheap, simple, and used for pole transformer protection.
Write a short note on drop-out fuse.
A drop-out fuse (expulsion fuse cut-out) is an outdoor fuse widely used on 11 kV and 33 kV distribution lines and pole-mounted distribution transformers in Nepal.
Construction:
- A porcelain or polymer insulator with upper and lower contacts, mounted on a cross-arm.
- A fuse tube (carrier) made of fibre-glass with an inner lining of horn fibre or boric acid, containing a tin or copper fuse link.
- The fuse link holds the tube in position against a spring at the top contact.
upper contact (latch)
┌┐
││ fuse tube with
││ fuse link inside
││
─┘└─ hinge at lower contact
tube drops (swings) down
when link melts
Operation:
- On overcurrent or fault, the fuse link melts and an arc forms inside the tube.
- The arc heat decomposes the fibre lining, producing de-ionising gases (expulsion action) that blow the arc out through the open bottom end at current zero.
- Melting of the link releases the latch; the tube drops out and hangs down by gravity, giving a visible isolation gap and clear indication from the ground.
Advantages: cheap, simple, visible indication of operation, provides isolation, easy re-fusing with an operating (hot) stick.
Limitations: noisy expulsion of gases and flame, limited breaking capacity, not current limiting, needs manual replacement of link.
Applications: protection of distribution transformers, spur lines and capacitor banks in rural/urban feeders.