4-pole shunt generator, wave wound, 3 kW

Short answer

Load current I_L = 3000/120 = 25 A, shunt field current I_sh = 120/60 = 2 A, so armature current I_a = 27 A. Wave winding has 2 parallel paths, so conductor current = 27/2 = 13.5 A. Generated emf E = V + I_a R_a + brush drop = 120 + 27×0.2 + 2 = 127.4 V.

A 4-pole dc shunt generator has wave wound armature. The armature and field winding resistances are 0.2 Ω0.2\ \Omega and 60 Ω60\ \Omega respectively. The brush contact drop is 1 volt per brush. The generator is delivering a power of 3 kW at 120 V. Calculate: (a) Total armature current coming out from the brush. (b) Current in each armature conductor. (c) Generator EMF (E).

In a shunt generator the armature current supplies both the load and the field: Ia=IL+IshI_a = I_L + I_{sh}. The generated emf must also cover the armature drop and the brush drop.

(a) Armature current

Load current:

IL=PV=3000120=25 AI_L = \frac{P}{V} = \frac{3000}{120} = 25\ \text{A}

Shunt field current:

Ish=VRsh=12060=2 AI_{sh} = \frac{V}{R_{sh}} = \frac{120}{60} = 2\ \text{A} Ia=IL+Ish=25+2=27 AI_a = I_L + I_{sh} = 25 + 2 = 27\ \text{A}

(b) Current in each armature conductor

A wave winding has A=2A = 2 parallel paths regardless of the number of poles.

Iconductor=IaA=272=13.5 AI_{\text{conductor}} = \frac{I_a}{A} = \frac{27}{2} = 13.5\ \text{A}

(c) Generated emf

Brush drop =1 V×2 brushes (one positive, one negative)=2 V= 1\ \text{V} \times 2\ \text{brushes (one positive, one negative)} = 2\ \text{V}.

E=V+IaRa+Vbrush=120+(27)(0.2)+2=120+5.40+2=127.40 V\begin{aligned} E &= V + I_aR_a + V_{brush} \\ &= 120 + (27)(0.2) + 2 \\ &= 120 + 5.40 + 2 = 127.40\ \text{V} \end{aligned}

Answer: (a) Ia=27 AI_a = 27\ \text{A}; (b) current per conductor =13.5 A= 13.5\ \text{A}; (c) E=127.40 VE = 127.40\ \text{V}.