Wave-wound shunt generator, power absorbed by load
Short answer
Generated emf E = (0.02×378×1000×4)/(60×2) = 252 V. Load and field in parallel with armature yield equivalent resistance 9.091 Ω. Armature current 24.973 A, terminal voltage 227.03 V. Load power = (227.03)²/10 = 5154 W.
A 4 pole d.c shunt generator with a field resistance of and an armature resistance of has 378 wave connected conductors in its armature. The flux per pole is 0.02 Wb. If a total resistance of is connected across the armature terminals and the generator is driven at 1000 rpm. Calculate the power absorbed by the load.
The load (10 Ω) and the field winding (100 Ω) are both across the armature terminals, so they are in parallel. The generated emf comes from the emf equation for a wave winding ().
Step 1: Generated emf
Step 2: Terminal resistance and armature current
Load in parallel with field:
Step 3: Terminal voltage
Step 4: Load current and power
(Check: .)
Answer: power absorbed by the load ( kW) at a terminal voltage of .
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Power to 10 Ω load from shunt generator · Electrical Machines I, chapter 3
- 4-pole shunt generator, wave wound, 3 kW · Electrical Machines, chapter 3 · asked 3×
- Long shunt compound generator speed, 300 conductors · Electrical Machines, chapter 3 · asked 2×
- Long shunt compound generator speed, lap and wave · Electrical Machines, chapter 3 · asked 2×
- Shunt motor speed with 0.1 Ω armature resistance, less load · Electrical Machines I, chapter 4 · asked 3×
- EMF and load resistance of short shunt compound generator · Electrical Machines I, chapter 3
- 4-pole shunt generator, 3 kW at 120 V · Electrical Machine, chapter 3 · asked 2×
- Armature dimensions of 50 kW shunt generator · Electric Machine Design, chapter 5
- DC shunt motor armature torque · Basic Electrical and Electronics Engineering, chapter 2
- Long shunt compound generator speed · Electrical Machine, chapter 3