Earthquake loads in RCC design
Short answer
Seismic weight W = dead load + percent live load; time period T = 0.075 h^0.75 for bare RC frames; design base shear Vb = Ah W with Ah = (Z/2)(I/R)(Sa/g); distribute over height as Qi = Vb Wi hi^2 / Σ Wj hj^2; apply combinations (1.5(DL±EL), 1.2(DL+LL±EL), 0.9DL±1.5EL) and detail per IS 13920.
How do you consider earthquake loads while designing RCC structures? Explain briefly.
Earthquake loads are considered as equivalent static lateral forces (or by response spectrum analysis for tall or irregular buildings), as per IS 1893 (Part 1) or, in Nepal, NBC 105:2020.
Steps
- Seismic weight = dead load + a percentage of the live load (25% if the live load is kN/m, 50% if it is more; roof live load is neglected).
- Time period of a bare RC frame: (s), with in m.
- Design base shear:
with from the zone map, the importance factor, the response reduction factor (5 for special moment resisting RC frames, 3 for ordinary ones) and from the spectrum for the soil type. 4. Distribute over the height: , and apply at each floor in both directions (plus 30% of the orthogonal force). 5. Load combinations (IS 1893 cl. 6.3; partial safety factors from IS 456 Table 18): , , , . 6. Design and detail the members for the worst combination, and provide ductile detailing as per IS 13920.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Earthquake design philosophy, strength and ductility · Design of RCC Structure, chapter 12
- Beam reinforcement for given loads, 6 m span · Design of RCC Structure, chapter 4
- Beam design, 250x475 section · Design of RCC Structure, chapter 4 · asked 2×
- Two-way slab on RCC beams, 4x6 m · Design of RCC Structure, chapter 9 · asked 2×
- Design simply supported beam, 6 m span · Design of RCC Structure, chapter 4
- Shear design with torsion, 250x500 · Design of RCC Structure, chapter 5
- Criteria for designing and laying out tunnels · Hydro Power, chapter 5 · asked 2×
- Types of loads on structures and effects · Mechanics of Solids, chapter 1
- RCC floor joist design, 15 m x 6 m hall · Design of Steel and Timber Structure, chapter 7
- Factors while routing signal traces on PCB · Instrumentation II, chapter 8 · asked 4×