- Practice · 3+5 marks
Ventilation standards and fresh-air requirement
Short answer
Using Q = G/(Ci - Co), generation is 0.052 L/s and concentration difference is 600 ppm, giving 0.0867 m³/s or 312 m³/h, which is 8.7 L/s per person. Room volume is 90 m³, so air changes per hour are 3.5.
(a) What is the purpose of ventilation standards? State two ways in which they are specified. (b) A classroom 6 m x 5 m x 3 m is occupied by 10 persons, each releasing 0.0052 L/s of CO2. The outdoor CO2 level is 400 ppm and the indoor level is to be kept at 1000 ppm. Calculate the fresh-air flow required (in m3/h and L/s per person) and the air changes per hour.
(a) Ventilation standards
A ventilation standard (e.g. ASHRAE 62.1) specifies the minimum outdoor air that must be supplied to a space so that the concentration of contaminants stays at a level acceptable to occupants. It protects health and comfort and is the basis for designing HVAC systems.
Ways of specifying:
- Ventilation rate procedure: a prescribed airflow per person (L/s per person) plus a component per unit floor area (L/s per ) for building-related sources, depending on the use of the space.
- Air change rate: the number of room volumes of fresh air supplied per hour (ACH), common for hospitals, kitchens and laboratories.
- (Also) Indoor air quality procedure: limiting the concentration of selected contaminants (e.g. a CO level about 700 ppm above outdoors, or total VOCs).
(b) Numerical
Mass balance at steady state: pollutant generation = removal by ventilation.
Generation: L/s /s.
Concentration difference: .
Per person: L/s per person.
Room volume :
Answer: Fresh air required = 312 m/h (86.7 L/s, i.e. 8.7 L/s per person); ACH = 3.5 per hour.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Indoor air pollutants and their sources · Environment and Pollution Control, chapter 3
- Control strategies for indoor air quality · Environment and Pollution Control, chapter 3
- Sound pressure level and power level calculations · Environment and Pollution Control, chapter 6
- Ca and Mg concentration, NCH, alkalinity: TH 400 ppm · Water Supply Engineering, chapter 4
- Building types, mechanical ventilation, air flow · Building Technology, chapter 1
- Outdoor propagation models (any two) · Wireless Communication, chapter 3 · asked 3×
- Indoor air pollution in Nepal and counter measures · Technology, Environment and Society, chapter 5