- 2074 Chaitra · 8 marks
AC voltage controller RL load at α = 90°
Short answer
Load angle is 38.15°, so conduction is discontinuous. Extinction angle β is found numerically as 215.37°. RMS output voltage is 169.99 V, RMS load current is 5.575 A.
The single phase ac controller has input voltage of 230V, 50Hz and the positive and negative thyristors are triggered at an angle of 90° and π+90° respectively. The series RL load has R = 20 Ω, L = 50mH then determine the rms value of load voltage and load current.
With an R-L load, current lags; since is greater than the load angle , conduction is discontinuous and each SCR conducts from to the extinction angle .
Given: V, 50 Hz, , mH, .
Load parameters
Since , conduction is discontinuous.
Extinction angle
Setting :
Solving numerically (trial and error):
Check: , so T1 stops before T2 is fired (discontinuous), as expected.
RMS load voltage
(Here rad, and .)
RMS load current
Evaluating with A gives
Check by power balance: W, equal to the average of .
Answer: , V, A.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- AC voltage controller RL load extinction angle · Power Electronics, chapter 6
- AC voltage controller rms at α = 90° · Power Electronics, chapter 6 · asked 2×
- Single-phase AC voltage controller with R load · Power Electronics, chapter 6 · asked 6×
- AC voltage controller, R = 20 Ω, α = 45° · Power Electronics, chapter 6 · asked 2×
- Three-phase AC-DC with three thyristors, inductive load · Power Electronics, chapter 3
- AC voltage controller, R = 10 Ω, α = 45° · Power Electronics, chapter 6 · asked 2×
- Input current, pf and torque of single phase IM · Electric Machines II, chapter 3
- 3-phase half controlled bridge: no-load speed, firing angle · Utilization of Electrical Energy, chapter 3 · asked 3×
- Overhang beam: ILD, max positive/negative moment at D · Theory of Structures I, chapter 5
- Series RL circuit with 283 sin(300t+90°) · Basic Electrical Engineering, chapter 6