- Asked 4/23
- 2076 Asoj · 8 marks
Three-phase single-way controlled rectifier, α = 30°
Short answer
With a highly inductive load current is continuous and constant; each thyristor conducts 120° and commutates when the next phase is fired. Vdc=0.827Vm cosα, so at α=30° Vdc=0.716Vm; Vrms=Vm[1/2+3√3cos2α/(8π)]^{1/2}. The α=30° waveform is continuous pulses just touching zero, from 60° to 180° for T1.
Explain the operation of three phase single way controlled rectifier with highly inductive load. Derive the expression of average and RMS value of output voltage. Draw the waveforms of output voltage for α = 30° and calculate average value of output voltage.
A three-phase single-way (half-wave, three-pulse) controlled rectifier uses three thyristors, one per phase, connected to a star-connected supply (or transformer secondary) with the load returned to the neutral. The output voltage is controlled by delaying the firing of each thyristor by from its natural commutation point. The load is highly inductive, so the load current is continuous and constant.
T1
a o------>|-----+
T2 |
b o------>|-----+------o P (+)
T3 | |
c o------>|-----+ Load
|
n o----------------------o N (-)
a, b, c, n: star-connected secondary
va = Vm sin wt, vb lags 120, vc lags 240
Operation
- Each thyristor's anode goes to one phase and the cathodes are joined to the positive output. A thyristor can conduct only when its phase is the most positive and it has been fired.
- The firing angle is measured from the natural commutation point (the instant a diode would start conducting), i.e. from after the zero crossing of its phase voltage. So T1 is fired at , T2 at , T3 at .
- When T2 is fired, , so T1 becomes reverse biased and turns off (natural/line commutation).
- With a highly inductive load, the load current is continuous and constant, so each thyristor conducts for exactly , even if its phase voltage becomes negative. The output follows the phase of the conducting thyristor.
| Interval () | Conducting | |
|---|---|---|
| – | T1 | |
| – | T2 | |
| – | T3 |
Waveform for α = 30°
phase: va vb vc
fired at: 60 180 300 (deg)
ends at: 180 300 420
each phase is used from 60 to 180 deg of its
own sine; vo just touches zero at the end
of each pulse (boundary of continuity)
vo
.-. .-. .-.
/ \ / \ / \
| \ | \ | \
-----+------+-----+------+-----+------+--
60 180 180 300 300 420
each pulse: 0.866 Vm -> Vm (at 90) -> 0
The thyristor currents are blocks of the constant load current .
Average output voltage
Taking the conduction of T1 (the waveform repeats every ):
where is the peak phase voltage. Maximum value (at ) is , so .
RMS output voltage
(using )
Calculation for α = 30°
Assumption: phase voltage 230 V (400 V line), V.
Answer: = 232.96 V (for 230 V per phase).
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Three-phase single-way controlled rectifier, R load · Power Electronics, chapter 3 · asked 3×
- Three-phase single-way thyristor rectifier: average and RMS · Power Electronics, chapter 3 · asked 5×
- Three-phase single-way controlled rectifier, α = 90° · Power Electronics, chapter 3 · asked 4×
- Three-phase single-way diode rectifier: average and rms · Power Electronics, chapter 3 · asked 2×
- Three-phase single-way controlled rectifier, α = π/6 · Power Electronics, chapter 3
- Three-phase single-way controlled rectifier, α = 60° · Power Electronics, chapter 3 · asked 3×
- Three-phase single-way controlled rectifier · Power Electronics, chapter 3 · asked 3×
- Three-phase single-way thyristor rectifier: average · Power Electronics, chapter 3 · asked 3×
- Full controlled rectifier, 25 A, α = 30°, derivation · Power Electronics, chapter 2
- Voltage regulation expression for inductive load · Electrical Machines, chapter 2